HomeMy WebLinkAboutDERR-2024-010199 WESTECH EQUIPMENT
195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307
801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054
PRESSURE/VACUUM VENT CAP
LEAK RATES AND OPENING PRESSURES
Facility Name: Smith’s #475 Owner: Smith’s Food and Drug Centers, Inc.
Address: 3171 East 3300 South Address: P.O. Box 305103
City, State, Zip: Salt Lake City, Utah 84109 City, State, Zip: Nashville, Tennessee 37230
Facility I.D.#: 4002338 Phone #: 801-977-2012
Testing Company: Westech Phone #: 801-266-2545 Date: 8/20/24
This procedure is to determine pressure/vent cap specifications. See 40 CFR 63 CCCCCC for the inspection procedure.
Tank Number 1/2
Product Grade RUL/PUL
PV Manufacturer OPW
Model Number 623V
PRESSURE TEST
Passing 2” Leak Rate (CFH) <0.05
Measured 2” Leak Rate (CFH) New Cap
Passing Positive Opening Pressure (Inches WC) 2.5 – 6.0
Measured Positive Opening Pressure (Inches WC) New Cap
VACUUM TEST
Passing -4” Leak Rate (CFH) <0.21
Measured -4” Leak Rate (CFH) New Cap
Passing Negative Opening Pressure (Inched WC) 6.0 – 10.0
Measured Negative Opening Pressure (Inched WC) New Cap
Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail
Comments: New PV cap installed 8/19/24
Tester’s Name Taber DeHart, UT-0394 Tester’s Signature