HomeMy WebLinkAboutDERR-2024-010056Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name CRETE CARRIER CORPORATION
Address 400 NW 56TH ST
LINCOLN, NE 68501
Contact CRETE CARRIER CORPORATION
Phone
Email None
TANK LOCATION
Name CRETE CARRIER CORP
Address 695 W 1100 N
NORTH SALT LAKE, UT 84054
A Operator MIKE LEPORE
Phone (801) 936-9031
B Operator SAME
Phone SAME
Facility ID: 3000393 Inspection Date: 08/19/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
TANK DETAILS
Tank ID/Alt ID 4 / 4
E-Gen/AST No / No
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc July 31, 1990 / 4000 / Single
Substance
Stored Used Oil /
Tank Material-
Mod
Fiberglass Reinforced Plastic-
Double-Walled
ATG Veeder Root / TLS-300
LTT Test None
LLD Test None
Pipe Material-Mod Fiberglass Reinforced Plastic
/ None
Pipe type/STP Cont Gravity Feed / No
STP Flex Connectors Not Listed
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / none /
Yes
PST Fund/Other
Type Yes / None
Tank/Pipe Rel Det TankATG PipeLDNotListed
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
None
2024-08-19 Page 1 of 4
FACILITY RESPONSES
The above accurately represents the
facility's release detection records Yes
Financial Responsibility
Financial responsibility method is ok?Yes
Operator Training
A Operator current?No
B Operator current?No
Monthly checklist available and
complete?Yes
Is the site unmanned?Yes
Is a sign posted in a conspicuous area
giving the name and telephone number
of a person in case of an emergency
and if the station is manned part of the
time, are C operators trained?
Yes
Does the site have emergency shutoff
device?Yes
TANK RESPONSES
Tank 4 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Is the spill containment bucket(s) able
to contain a spill? (i.e. is there water,
product, debris, etc in the spill bucket
to prevent it from containing a spill?)
Yes
Tank has an overfill device?Yes
Tank is exempt from this requirement?Yes
Tank 4 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
Tank 4 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Tank 4 ATG/IM
ATG/IM - Records on site document that
the system is properly installed,
calibrated, operated, and maintained
(system and tank setup reports,
maintenance records)? Written
documentation of calibration,
maintenance, and repair is kept for at
least one year after work is completed?
Yes
ATG/IM - ATG console or other
equipment used to take readings and
perform tests is adequate, accessible,
and operational?
Yes
ATG/IM - Documentation of valid testing
or monitoring is available (must have
records for the two most recent months
and 10 of last 12 months)? Show results
in the RD tab.
Yes
ATG - The tank was filled to at least the
minimum level required to ensure a
valid leak test, and the tank size is
within the allowed upper and lower size
limits?
Yes
Tank 4 ATG/IM
Does the ATG system have a valid
annual test?Yes
DISPENSER RESPONSES
2024-08-19 Page 2 of 4
MONTHLY LEAK DETECTION MONITORING
Aug '23 Sep '23 Oct '23 Nov '23 Dec '23 Jan '24 Feb '24 Mar '24 Apr '24 May '24 Jun '24 Jul '24
Tank 4 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
FACILITY
No Photos
Question:A Operator current?
Comments:None
FACILITY
No Photos
Question:B Operator current?
Comments:None
Inspection Information
Inspector:Harris, Gary
Record Created:Aug. 19, 2024, noon
Inspection Date:Aug. 19, 2024
2024-08-19 Page 3 of 4