DERR-2024-009980
WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 STATIC PRESSURE DECAY TEST Facility Name: Smith’s #66 Owner: Smith’s Food and Drug Centers, Inc. Address: 4065 South Redwood Road Address: P.O. Box 305103 City, State, Zip: Taylorsville, Utah 84123 City, State, Zip: Nashville, Tennessee 37230 Facility I.D.#: 4002267 Phone #: 801-977-2012 Testing Company: Westech Phone #: 801-266-2545 Date: 4/1/24 This procedure is to determine static pressure decay. See 40 CFR 63 CCCCCC for the inspection procedure. Tank Number 1 2 1/2 Product Grade RUL PUL RUL/PUL Manifolded ☒Yes ☐No ☒Yes ☐No ☒Yes ☐No ☐Yes ☐No Actual Tank Volume (gallons) 14,544 6,786 Fuel Volume (gallons) 8,816 3,584 Ullage Volume (gallons) 5,728 3,202 8,930 Number of Nozzles Served 8 8 8 DECAY TEST Initial Pressure (Inches WC) 2.00 Pressure after 1 Minute (Inches WC) 2.00 Pressure after 2 Minutes (Inches WC) 1.97 Pressure after 3 Minutes (Inches WC) 1.96 Pressure after 4 Minutes (Inches WC) 1.96 Final Pressure after 5 Minutes (Inches WC) 1.96 Allowable Final Pressure (Inched WC) 1.83 Test Results ☐Pass ☐Fail ☐Pass ☐Fail ☒Pass ☐Fail ☐Pass ☐Fail Comments: Tester’s Name Taber DeHart, UT-0394 Tester’s Signature WESTECH EQUIPMENT 195 WEST 3900 SOUTH • P.O. BOX 57307 • SALT LAKE CITY, UTAH 84157-0307 801-266-2545 • TOLL FREE 800-433-8831 • 24 HOUR FAX 801-261-4054 PRESSURE/VACUUM VENT CAP LEAK RATES AND OPENING PRESSURES Facility Name: Smith’s #66 Owner: Smith’s Food and Drug Centers, Inc. Address: 4065 South Redwood Road Address: P.O. Box 305103 City, State, Zip: Taylorsville, Utah 84123 City, State, Zip: Nashville, Tennessee 37230 Facility I.D.#: 4002267 Phone #: 801-977-2012 Testing Company: Westech Phone #: 801-266-2545 Date: 4/1/24 This procedure is to determine pressure/vent cap specifications. See 40 CFR 63 CCCCCC for the inspection procedure. Tank Number 1/2 Product Grade RUL/PUL PV Manufacturer OPW Model Number 623V PRESSURE TEST Passing 2” Leak Rate (CFH) <0.05 Measured 2” Leak Rate (CFH) New Cap Passing Positive Opening Pressure (Inches WC) 2.5 – 6.0 Measured Positive Opening Pressure (Inches WC) New Cap VACUUM TEST Passing -4” Leak Rate (CFH) <0.21 Measured -4” Leak Rate (CFH) New Cap Passing Negative Opening Pressure (Inched WC) 6.0 – 10.0 Measured Negative Opening Pressure (Inched WC) New Cap Test Results ☒Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail ☐Pass ☐Fail Comments: New PV cap installed Tester’s Name Taber DeHart, UT-0394 Tester’s Signature