Loading...
HomeMy WebLinkAboutDDW-2024-010003Sanitary Survey - Deficiency Report PWS Number:UTAH09045 Deficiency Points:50 Survey Date:07/30/2024 Survey Name:BRYCE CANYON NATIONAL PARK Surveyor:Brian Pattee Sanitary Survey Category: TR SDWIS Severity Code: Significant Deficiency Treatment - Chlorination General | TP001 | WELLS CHLORINATOR/ BAG FILTER 132. Chlorine (gas & hypochlorite solution, tablets, granules, ) and chemicals used to generate chlorine solutions and chlorine dioxide meet ANSI/NSF 60. Rule: R309-525-11(5), R309-520-6(2)All chemicals added to drinking water, including chlorine, chloramines and chemicals used to generate hypochlorite solutions and chlorine dioxide, shall be certified as complying with ANSI/NSF Standard 60. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Liquid Chlorine Is not NSF 60 , appears to be for Pool and Hot Tubs , could not find a listed NSF 60 standard for Sodium Hypochlorite being used . Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: TD90 ADDING CHEMICALS THAT DO NOT MEET ANSI NSF 60 STANDARD