HomeMy WebLinkAboutDDW-2024-009882Sanitary Survey - Deficiency Report
PWS Number:UTAH09105 Deficiency Points:170 Survey Date:07/30/2024
Survey Name:UNDER CANVAS BRYCE
CANYON
Surveyor:Brian Pattee
Sanitary Survey Category: SM
SDWIS Severity Code: Significant Deficiency
General Maintenance and Environment | DS001 | UTAH09105 DISTRIBUTION SYSTEM
42. Are there any visual indications of unsanitary conditions?
Rule: R309-200-6, R309-105-18, R309-215-4(3)R309-200-6 The Secondary Maximum Contaminant Levels for public water systems
deals with substances which affect the aesthetic quality of drinking water. They are
presented here as recommended limits or ranges and are not grounds for rejection. The
taste of water may be unpleasant and the usefulness of the water may be impaired if
these standards are significantly exceeded.
R309-105-18 The Director or the local health department shall be informed by
telephone by a water supplier of any "emergency situation". The term "emergency
situation...
R309-215-4(3) If the water fails to meet minimum standards, then certain public
notification procedures shall be carried out, as outlined in R309-220. Water suppliers
shall also keep analytical records in their possession, for a required length of time, as
outlined in R309-105-17.
Notes:Storage Tank Hatch lids are rusted on the inside . Middle tank had what appeared to be
floating roots , or weeds of some kind , all 3 tanks are sinking and listing heavily to one side
, the side where all the piping connections are to the system , potentialy being compromised.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: M017 WATER STAGNATION, BIOFILM OR SEDIMENTS CONTRIBUTES TO DRINKING
WATER CONTAMINATION
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | TANK 1 - WEST TANK
83. Area surrounding ground-level or buried storage tank is graded to prevent surface water from standing within 50 feet.
Rule: R309-545-7(4)Rule requires the area surrounding a ground-level or buried water storage tank be
graded in a manner to prevent surface water from standing within 50 feet of the tank.
This significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:All 3 buried storage tanks appear to be sinking & tilting off center , They sit in Large Hole
with evidence of water ponding .
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V001 STORAGE TANK SURROUNDING AREA NOT GRADED TO PREVENT STANDING
WATER WITHIN 50 FEET OF THE TANK
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | TANK 1 - WEST TANK
84. Storage tank roof is sloped to prevent ponding
Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding.
Notes:All 3 buried storage tanks appear to be sinking & tilting off center , They sit in Large Hole
with evidence of water ponding .
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO
DRAIN
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | TANK 2 - MIDDLE TANK
97. Area surrounding ground-level or buried storage tank is graded to prevent surface water from standing within 50 feet.
Rule: R309-545-7(4)Rule requires the area surrounding a ground-level or buried water storage tank be
graded in a manner to prevent surface water from standing within 50 feet of the tank.
This significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:All 3 buried storage tanks appear to be sinking & tilting off center , They sit in Large Hole
with evidence of water ponding .
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V001 STORAGE TANK SURROUNDING AREA NOT GRADED TO PREVENT STANDING
WATER WITHIN 50 FEET OF THE TANK
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST002 | TANK 2 - MIDDLE TANK
98. Storage tank roof is sloped to prevent ponding
Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding.
Notes:All 3 buried storage tanks appear to be sinking & tilting off center , They sit in Large Hole
with evidence of water ponding .
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO
DRAIN
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST003 | TANK 3 EAST TANK
111. Area surrounding ground-level or buried storage tank is graded to prevent surface water from standing within 50 feet.
Rule: R309-545-7(4)Rule requires the area surrounding a ground-level or buried water storage tank be
graded in a manner to prevent surface water from standing within 50 feet of the tank.
This significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:All 3 buried storage tanks appear to be sinking & tilting off center , They sit in Large Hole
with evidence of water ponding .
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V001 STORAGE TANK SURROUNDING AREA NOT GRADED TO PREVENT STANDING
WATER WITHIN 50 FEET OF THE TANK
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST003 | TANK 3 EAST TANK
112. Storage tank roof is sloped to prevent ponding
Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding.
Notes:All 3 buried storage tanks appear to be sinking & tilting off center , They sit in Large Hole
with evidence of water ponding .
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO
DRAIN