HomeMy WebLinkAboutDDW-2024-009865Sanitary Survey - Deficiency Report
PWS Number:UTAH02031 Deficiency Points:15 Survey Date:07/23/2024
Survey Name:GIRLS HOME Surveyor:Cameron Draney
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Treatment - General | TP001 | GIRLS HOME FILTRATION
92B. There are adequate spill containment provisions for acid and caustic liquids.
Rule: R309-525-11(6)(a)(iv)(B), R309-525-
11(8)(b)(viii)
Rule requires liquid chemical storage tanks to have an overflow and receiving basin or
drain capable of receiving accidental spills or overflows, and meeting all the
requirements of R309-525-23.
Notes:Spill containment required for citric acid.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TG59 LACKS CONTAINMENT PROVISIONS TO HANDLE SOLUTION TANK SPILLS OR
OVERFLOWS