HomeMy WebLinkAboutDDW-2024-009721Sanitary Survey - Deficiency Report
PWS Number:UTAH22002 Deficiency Points:115 Survey Date:07/23/2024
Survey Name:COALVILLE CITY WATER
SYSTEM
Surveyor:Julie Cobleigh
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS004 | LEWIS HOLLOW WELL
100A. Pump to waste line discharges with a minimum of 12-inch clearance to flood rim
Rule: R309-515-6(12)(d)(ix)Rule requires a pump-to-waste line connected to a sewer/storm drain to have a
minimum 12-inch clearance to the flood rim. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:buried
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S009 PUMP TO WASTE LINE LACKS PROPER AIR GAP
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS004 | LEWIS HOLLOW WELL
100B. Pump to waste line equipped with #4 non-corrodible mesh screen
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be covered with a No. 4 mesh
corrosion-resistant screen. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:buried
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S010 END OF WELL PUMP-TO-WASTE LINE LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS004 | LEWIS HOLLOW WELL
100C. Pump to waste line downturned if it discharges to sewer/storm drain or allowing complete drainage if not downturned
Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be downturned. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:buried
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S011 WELL PUMP TO WASTE LINE NOT DOWNTURNED
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | OLD ICY SPRING RESERVOIR
125A. Mild deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust.
Notes:some cracks have been sealed but others are not
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE
DETERIORATION
Sanitary Survey Category: MR
SDWIS Severity Code: Significant Deficiency
Treatment - Chlorination General | TP001 | ICY SPRING CHLORINATOR
207. Daily operating records reflect chemical dosages and total quantities used
Rule: R309-105-14(3)(a)Rule requires all water system using chemical addition or specialized equipment for the
treatment of drinking water to regularly complete operational reports. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:only recording chemical quantities used and flow 3 times a week
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TG20 DAILY RECORDS DO NOT REFLECT DOSAGES ACCURATELY