HomeMy WebLinkAboutDDW-2024-009671Sanitary Survey - Deficiency Report
PWS Number:UTAH04060 Deficiency Points:25 Survey Date:07/15/2024
Survey Name:STARPOINT CAMP Surveyor:Chris Martin
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | STORAGE TANK ST001
86A. Overflow line discharges at least 12 inches above ground or the flood rim of receiving basin?
Rule: R309-545-13 Rule requires all water storage tanks to be provided with an overflow that discharges at
an elevation between 12 and 24 inches above the ground surface or the rim of the
receiving basin.
Notes:The overflow line seems to terminate below the flood rim of the receiving basin.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V011 END OF STORAGE TANK OVERFLOW LACKS A CLEARANCE OF BETWEEN 12
AND 24 INCHES FROM GROUND SURFACE