HomeMy WebLinkAboutDDW-2024-009669Sanitary Survey - Deficiency Report PWS Number:UTAH14012 Deficiency Points:65 Survey Date:07/19/2024 Survey Name:LEAMINGTON TOWN WATER SYSTEM Surveyor:John Chartier Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST001 | OLDER CONCRETE TANK 133B. Overflow line covered with #4 mesh non-corrodible screen Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens installed at a location least susceptible to damage by vandalism. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:The overflow discharge was missing the #4 screen, it appeared to have been a screen with a plastic collar and it was accidentally burned when the canal banks were burned in the spring. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Gaseous Chlorination | TP002 | UP AND LOW NARROWS CHLORINATOR 187. Air inlets are located near the ceiling and fitted with louvers. Rule: R309-520-7(2)(d)(iv)Rule requires chlorine room air inlets to be through wall louvers near the ceiling. Notes:An air vent will be placed at the top end of the entry door to correct this deficiency. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TD10 CHLORINE ROOM AIR INLET NOT LOCATED NEAR CEILING THROUGH WALL LOUVERS Sanitary Survey Category: TR SDWIS Severity Code: Significant Deficiency Gaseous Chlorination | TP002 | UP AND LOW NARROWS CHLORINATOR 188. Chlorine vent line discharges outside and above grade and is screened with #14 mesh screen. Rule: R309-520-7(2)(e)Rule requires the chlorine vent line to discharge outside, above grade, at a point least susceptible to vandalism, and to have the end covered with a #14 mesh non-corrodible screen. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Screen needs to be replaced on the chlorine vent lines from both regulators. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: TD13 CHLORINE VENT LINE NOT DISCHARGED OUTSIDE ABOVE GRADE OR LACKS NO. 14 SCREEN