HomeMy WebLinkAboutDDW-2024-009669Sanitary Survey - Deficiency Report
PWS Number:UTAH14012 Deficiency Points:65 Survey Date:07/19/2024
Survey Name:LEAMINGTON TOWN
WATER SYSTEM
Surveyor:John Chartier
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | OLDER CONCRETE TANK
133B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:The overflow discharge was missing the #4 screen, it appeared to have been a screen with a
plastic collar and it was accidentally burned when the canal banks were burned in the
spring.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP002 | UP AND LOW NARROWS CHLORINATOR
187. Air inlets are located near the ceiling and fitted with louvers.
Rule: R309-520-7(2)(d)(iv)Rule requires chlorine room air inlets to be through wall louvers near the ceiling.
Notes:An air vent will be placed at the top end of the entry door to correct this deficiency.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD10 CHLORINE ROOM AIR INLET NOT LOCATED NEAR CEILING THROUGH WALL
LOUVERS
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Gaseous Chlorination | TP002 | UP AND LOW NARROWS CHLORINATOR
188. Chlorine vent line discharges outside and above grade and is screened with #14 mesh screen.
Rule: R309-520-7(2)(e)Rule requires the chlorine vent line to discharge outside, above grade, at a point least
susceptible to vandalism, and to have the end covered with a #14 mesh non-corrodible
screen. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:Screen needs to be replaced on the chlorine vent lines from both regulators.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD13 CHLORINE VENT LINE NOT DISCHARGED OUTSIDE ABOVE GRADE OR LACKS
NO. 14 SCREEN