HomeMy WebLinkAboutDDW-2024-009653Sanitary Survey - Deficiency Report
PWS Number:UTAH03077 Deficiency Points:150 Survey Date:07/23/2024
Survey Name:LODGE CAMPGROUND -
LOMIA GIRLS CAMP
Surveyor:Colt Smith
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | LODGE SPRING
56A. Overflow screened with #4 mesh screen
Rule: R309-515-7(7)(d), R309-545-13(3)Overflow pipes on junction and collection boxes shall comply with R309-545 and be
screened with No. 4 mesh non-corrodible screens. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Screen was broken at time of inspection.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS04 SPRING BOX OVERFLOW LACKS NO. 4 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | LODGE SPRING
56B. Overflow has a minimum of 12 inch clearance above flood rim of receiving basin
Rule: R309-515-7(7)(d), R309-545 Overflow pipes on junction and collection boxes shall comply with R309-545 and
discharge a minimum of 12 inches above the ground surface or rim of the receiving
basin. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:The overflow lacked clearance and very near open water.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS14 SPRING BOX OVERFLOW OR DRAIN LACKS FREE FALL OF 12 TO 24 INCHES
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | LODGE SPRING
57. Drain has minimum of 12 inch clearance above flood rim of receiving basin
Rule: R309-515-7(7)(d), R309-545 Overflow pipes on junction and collection boxes shall comply with R309-545 and
discharge a minimum of 12 inches above the ground surface or rim of the receiving
basin. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:The drain lacked clearance and very near open water.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS14 SPRING BOX OVERFLOW OR DRAIN LACKS FREE FALL OF 12 TO 24 INCHES
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | LODGE SPRING
60. No deep-rooted vegetation is within the 50 ft collection area.
Rule: R309-515-7(7)(f)All deep-rooted vegetation within the fenced collection area shall be removed by a
means not negatively affecting water quality. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:There are willows taking root in the collection area.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS07 DEEP ROOTED VEGETATION IN SPRING COLLECTION AREA
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | LODGE SPRING
61. No roots seen in collection boxes and junctions.
Rule: R309-105-10(4)(a), R309-515-8(1)(a)Spring collection areas shall be periodically (preferably annually) cleared of deep-
rooted vegetation to prevent root growth from clogging collection lines. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:There were roots in the collection box.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS08 ROOTS IN SPRING COLLECTION PIPES
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | LODGE SPRING
62E. Spring box lid is locked
Rule: R309-515-7(7)(d), R309-545-14 (3)Access openings shall comply with R309-545 and the lids to the openings shall be
locked. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:We had to cut the lock to access the spring box.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS13 SPRING BOX LID IS NOT LOCKED