HomeMy WebLinkAboutDDW-2024-009543Sanitary Survey - Deficiency Report
PWS Number:UTAH09017 Deficiency Points:40 Survey Date:07/07/2023
Survey Name:PINE LAKE CAMPGROUND Surveyor:Luke Treutel
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | PINE LAKE SPRING
64. Is a spring collection box present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box
to permit spring inspection and testing.
Notes:No spring box present
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | PINE LAKE SPRING
65. Is a spring box vent present? ... if yes, answer the following question(s)
Rule: R309-515-7(7)(d), R309-545-15 Rule requires junction boxes and collection boxes to comply with R309-545 with respect
to venting. Therefore, a junction or collection box requires a vent to be fitted with #14
mesh or finer non-corrodible screen, be fitted with a protective heavy-gauge screen or
covering if 6 inches in diameter or greater, be down-turned and shielded to prevent the
entrance of contaminants, be located and sized to avoid blockage during winter, and
have the end of the vent discharge a minimum of 24 inches above the earth on buried
structures.
Notes:No spring box present
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS11 SPRING BOX LACKS A MEANS OF VENTING
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | PINE LAKE SPRING
66. Spring has a permanent flow-measuring device.
Rule: R309-515-7(7)(h)Rule requires a spring to have a permanent flow measuring device.
Notes:No flow measuring device present
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS01 LACKS A PERMANENT DEVICE FOR MEASURING SPRING FLOW
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | 8K STEEL TANK
73B. Access opening shoe box type with at least 2 inches of overlap
Rule: R309-545-14(2)Rule requires the frame of an access opening to be provided with a close fitting solid
shoebox type cover which extends down around the frame at least two inches and is
furnished with a gasket(s) between the lid and frame. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:Lid only had 1 inch overlap. This was addressed prior to survey report being submitted. 2
inch overlap now present; deficiency resolved.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V010 STORAGE TANK LID NOT SHOEBOX STYLE