HomeMy WebLinkAboutDDW-2024-009535Sanitary Survey - Deficiency Report
PWS Number:UTAH15012 Deficiency Points:115 Survey Date:06/26/2023
Survey Name:RICHVILLE Surveyor:Sarah Romero Rivera
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Management and Operations | DS001 | UTAH15012 DISTRIBUTION SYSTEM
28B. System lacks more than 20% of required source capacity
Rule: R309-510-7(1)Rule requires a water system's source capacity to legally and physically meet the peak
day demand and the average yearly demand. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:System will complete operating permit for proposed well to meet required source capacity.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S094 SYSTEM LACKS MORE THAN 20% OF REQUIRED SOURCE CAPACITY
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH15012 DISTRIBUTION SYSTEM
29A. System lacks required storage capacity due to fire demand
Rule: R309-510-8(1)(b)Rule requires a public water system to provide equalization storage volume (to meet
average day demands for indoor and irrigation water use), fire flow storage volume (if
equipped with fire hydrants for fire suppression or required by the local fire code
official), and emergency storage (if deemed appropriate by the water system or the
Director).
Notes:The system has a storage capacity deficit of 27,651 gallons due to the required fire demand.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: VF34 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT
HAS SOP FOR FOLLOWING FIRE INCIDENT
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Springs | WS001 | TAGGART HOLLOW SPRING
57A. Overflow screened with #4 mesh screen
Rule: R309-515-7(7)(d), R309-545-13(3)Overflow pipes on junction and collection boxes shall comply with R309-545 and be
screened with No. 4 mesh non-corrodible screens. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Overflow has a screen that is No.2. System will replace the No.2 screen with a No.4 mesh
screen.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: SS04 SPRING BOX OVERFLOW LACKS NO. 4 SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | ELK HAVEN TANK
92B. Overflow line covered with #4 mesh non-corrodible screen
Rule: R309-545-13(3)Rule requires overflow pipes to be screened with #4 mesh non-corrodible screens
installed at a location least susceptible to damage by vandalism. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Overflow line covered with a No.2 mesh screen. The system will replace it with a No.4 mesh
screen.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V012 END OF STORAGE TANK OVERFLOW PIPE LACKS NO. 4 SCREEN