Loading...
HomeMy WebLinkAboutDDW-2024-009527Sanitary Survey - Deficiency Report PWS Number:UTAH07005 Deficiency Points:75 Survey Date:08/02/2023 Survey Name:NEOLA WATER AND SEWER DISTRICT Surveyor:Joe Hadlock Sanitary Survey Category: FW SDWIS Severity Code: Significant Deficiency Storage Tanks | ST002 | 0.5 MG TANK 120C. Vent covered with #14 or finer non-corrodible mesh screen. Rule: R309-545-15(4)Rule requires a water storage tank vent to be fitted with #14 mesh or finer non- corrodible screen and vents 6-inches or greater in diameter to be fitted with additional heavy gauge screen or substantial covering to protect the #14 mesh screen from vandalism or damage. This significant deficiency must be corrected within 120 days of notification or have a compliance action plan approved by DDW. Notes:Vent was missing screen. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: V007 STORAGE TANK VENT LACKS NO. 14 SCREEN Sanitary Survey Category: PU SDWIS Severity Code: Significant Deficiency Pump Stations | PF001 | UPPER SPRINGS BOOSTER PUMP 134. There are no unprotected cross-connections in the pump station. Rule: R309-105-12(1)Cross connections are not allowed unless controlled by an approved and properly operating backflow prevention assembly or device. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:Collection taps are threaded, not smooth nosed. Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: PS15 PUMP STATION HAS CROSS CONNECTION OR IS SUBJECT TO CONTAMINATION