HomeMy WebLinkAboutDDW-2024-009519Sanitary Survey - Deficiency Report
PWS Number:UTAH03010 Deficiency Points:45 Survey Date:08/01/2023
Survey Name:LOGAN CITY WATER
SYSTEM
Surveyor:Brian Pattee
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH03010 DISTRIBUTION SYSTEM
30A. System lacks up to 20% of required storage capacity (fire demand not included)
Rule: R309-510-8(1)(a)Rule requires a public water system to provide equalization storage volume (to meet
average day demands for indoor and irrigation water use), fire flow storage volume (if
equipped with fire hydrants for fire suppression or required by the local fire code
official), and emergency storage (if deemed appropriate by the water system or the
Director).
Notes:deficiency still valid
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V031 SYSTEM LACKS UP TO 20% OF REQUIRED STORAGE CAPACITY (FIRE DEMAND
NOT INCLUDED)
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | GOLF COURSE 3
183. Storage tank roof is sloped to prevent ponding
Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding.
Notes:Ponding on Roof
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO
DRAIN
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST002 | GOLF COURSE 4
197. Storage tank roof is sloped to prevent ponding
Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding.
Notes:Ponding on Roof
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO
DRAIN