Loading...
HomeMy WebLinkAboutDDW-2024-009519Sanitary Survey - Deficiency Report PWS Number:UTAH03010 Deficiency Points:45 Survey Date:08/01/2023 Survey Name:LOGAN CITY WATER SYSTEM Surveyor:Brian Pattee Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH03010 DISTRIBUTION SYSTEM 30A. System lacks up to 20% of required storage capacity (fire demand not included) Rule: R309-510-8(1)(a)Rule requires a public water system to provide equalization storage volume (to meet average day demands for indoor and irrigation water use), fire flow storage volume (if equipped with fire hydrants for fire suppression or required by the local fire code official), and emergency storage (if deemed appropriate by the water system or the Director). Notes:deficiency still valid Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V031 SYSTEM LACKS UP TO 20% OF REQUIRED STORAGE CAPACITY (FIRE DEMAND NOT INCLUDED) Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST001 | GOLF COURSE 3 183. Storage tank roof is sloped to prevent ponding Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding. Notes:Ponding on Roof Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO DRAIN Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Storage Tanks | ST002 | GOLF COURSE 4 197. Storage tank roof is sloped to prevent ponding Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding. Notes:Ponding on Roof Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO DRAIN