dwadmin@utah.gov <dwadmin@utah.gov>
to ddw_sanitarysurvey@utah.gov, jchartier@utah.gov, jd@gunnisoncity.org, elarsen@centralutahhealth.org
JD, Thank you for helping me complete the sanitary survey of the Gunnison City drinking water system.
The Utah Division of Drinking Water's Improvement Priority System (IPS) Rule, R309-400, rates public drinking water systems. Points are assigned based on non comp
if not corrected within the time frame speci ed in this report. Community systems that exceed 150 points will be rated as Not Approved if corrections are not made (N
De ciencies associated with inactive facilities show up on the accompanying De ciency Report to act as a tracking tool and reminder but are considered "pending" an
active in the future, the pending de ciencies will also become active. Your IPS report is available at waterlink.utah.gov and should be updated within a few days.
Attached are copies of the completed survey questions and resulting De ciency Report, as well as the Capacity Calculations spreadsheet.
Whenever a signi cant de ciency has been identi ed during a sanitary survey you must consult with the Division of Drinking Water regarding the appropriate correctiv
signi cant de ciencies must be corrected within 120 days of the date of completion of the survey or the system must enter into a corrective action plan with the Divis
(correction action) you must notify the Division and provide documentation of that correction within 30 days of the completing the correction. Failure to do so will resu
De ciencies given as a result of this sanitary survey include:
1. The lack of source capacity. With the Christensen Well o ine, the calculations show the City being about 12% de cient on source capacity. This is something that n
2. The missing screen on the chlorine vent line is a Signi cant De ciency, so please correct that and notify me as quickly as possible.
3. The ammonia bottle was missing in the chlorine room. It is recommended to keep a bottle of ammonium hydroxide in the chlorine room to check for chlorine gas le
We encourage you to take the necessary actions to correct the noted de ciencies. Once the de ciencies are corrected, please coordinate with our o ce at ddwips@u
number in all your correspondence to our o ce.
**** For further correspondence, hit Reply All and remove dwadmin@utah.gov, as it is not monitored. ****
2023 UTAH2000…2023 UTAH2000…Capacity Calc 20…
Reply all Reply to author Forward
2023 UTAH20004 | GUNNISON CITY Sanitary Survey - Results