Loading...
HomeMy WebLinkAboutDDW-2024-009503Sanitary Survey - Deficiency Report PWS Number:UTAH20004 Deficiency Points:55 Survey Date:07/12/2023 Survey Name:GUNNISON CITY Surveyor:John Chartier Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH20004 DISTRIBUTION SYSTEM 28A. System lacks up to 20% of required source capacity Rule: R309-510-7(1)Rule requires a water system's source capacity to legally and physically meet the peak day demand and the average yearly demand. Notes:Required source capacity is 1,366 gpm, Available source capacity is 1,205 gpm. Source capacity deficit is 11.8% Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S091 SYSTEM LACKS UP TO 20% OF REQUIRED SOURCE CAPACITY Sanitary Survey Category: TR SDWIS Severity Code: Significant Deficiency Gaseous Chlorination | TP004 | ARSENIC WTP 229. Chlorine vent line discharges outside and above grade and is screened with #14 mesh screen. Rule: R309-520-7(2)(e)Rule requires the chlorine vent line to discharge outside, above grade, at a point least susceptible to vandalism, and to have the end covered with a #14 mesh non-corrodible screen. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:The vent line is missing the #14 screen. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: TD13 CHLORINE VENT LINE NOT DISCHARGED OUTSIDE ABOVE GRADE OR LACKS NO. 14 SCREEN Sanitary Survey Category: TR SDWIS Severity Code: Minor Deficiency Gaseous Chlorination | TP004 | ARSENIC WTP 234B. Bottle of ammonium hydroxide (56 % ammonia solution) is available for chlorine leak detection Rule: R309-520-7(2)(l)(i)Rule requires a bottle of ammonium hydroxide (56% ammonia solution) to be available for leak detection. Notes:No ammonia hydroxide at the treatment building. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: TD14 NO AMMONIA HYDROXIDE SOLUTION FOR CHLORINE LEAK DETECTION