HomeMy WebLinkAboutDDW-2024-009503Sanitary Survey - Deficiency Report
PWS Number:UTAH20004 Deficiency Points:55 Survey Date:07/12/2023
Survey Name:GUNNISON CITY Surveyor:John Chartier
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH20004 DISTRIBUTION SYSTEM
28A. System lacks up to 20% of required source capacity
Rule: R309-510-7(1)Rule requires a water system's source capacity to legally and physically meet the peak
day demand and the average yearly demand.
Notes:Required source capacity is 1,366 gpm, Available source capacity is 1,205 gpm. Source
capacity deficit is 11.8%
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S091 SYSTEM LACKS UP TO 20% OF REQUIRED SOURCE CAPACITY
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Gaseous Chlorination | TP004 | ARSENIC WTP
229. Chlorine vent line discharges outside and above grade and is screened with #14 mesh screen.
Rule: R309-520-7(2)(e)Rule requires the chlorine vent line to discharge outside, above grade, at a point least
susceptible to vandalism, and to have the end covered with a #14 mesh non-corrodible
screen. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:The vent line is missing the #14 screen.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD13 CHLORINE VENT LINE NOT DISCHARGED OUTSIDE ABOVE GRADE OR LACKS
NO. 14 SCREEN
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Gaseous Chlorination | TP004 | ARSENIC WTP
234B. Bottle of ammonium hydroxide (56 % ammonia solution) is available for chlorine leak detection
Rule: R309-520-7(2)(l)(i)Rule requires a bottle of ammonium hydroxide (56% ammonia solution) to be available
for leak detection.
Notes:No ammonia hydroxide at the treatment building.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TD14 NO AMMONIA HYDROXIDE SOLUTION FOR CHLORINE LEAK DETECTION