HomeMy WebLinkAboutDDW-2024-009487Sanitary Survey - Deficiency Report
PWS Number:UTAH26037 Deficiency Points:5 Survey Date:10/13/2023
Survey Name:HEBER EAST STAKE
CENTER
Surveyor:Leslie Freeman
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Wells | WS001 | EAST STAKE WELL
63. Well discharge line has a smooth-nosed sampling tap, which samples the well water before any chemical injection. (first item from the
wellhead).
Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with a smooth nosed sampling tap, a
check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. (smooth
nosed sampling tap being the first item from the well head and the shut-off valve as the
last item)
Notes:No sampling tap.
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: S023 NO SMOOTH NOSED SAMPLING TAP ON DISCHARGE PIPING