HomeMy WebLinkAboutDDW-2024-009330Contacts
Type: Administrative Contact
Name: ANDREW CLARK BEECHER
Office: 801-240-1693
Emergency:
Email:
andrew.beecher@churchofjesuschrist.o
rg
acbeecher24@gmail.com
Site Information
Legal Contact: CORP OF PRESIDING
BISHOP- LDS CHURCH
Address: 50 E NORTH TEMPLE ST,
RM 1205 NATURAL RESOURCE
SERVICES, SALT LAKE CITY, UT
84150-6320
Phone: 801-240-1693
County: CACHE COUNTY
System Type: Transient Non-
Community
Certification Required:
Total Population: 50
Local Health District: Bear River
Health Department
Site Updates
Last Inventory Update: 01/02/2024
Last Surveyor Update: 06/04/2024
Surveyor: BRIAN H PATTEE
Operating Period: 5/1 - 9/30
Last IPS Update: 07/18/2024 08:56:32
System is required to disinfect as of
11/01/2021
Political Districts
Legislative District Map
Water Usage Information per ERC
Total Ips Points: 215
Public Water System IPS ReportDEQ | Drinking Water
Cinnamon Creek Rec Area PWS ID: UTAH03105 Rating: Approved 08/23/2012 Status: Active
IPS SUMMARY Total IPS Points: 215
Admin & Physical Facilities Quality & Monitoring Significant Deficiency Violations
90 25 100
PHYSICAL FACILITY POINTS Total Pts: 90
Facility Facility Name Status Points Effective Details
ST001 AREA A & B TANK A 0 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
V009
STORAGE TANK LID
LACKS A
FUNCTIONING
GASKET BETWEEN
THE LID AND FRAME
SIG Gaskets are deteriorating , Need replaced 06/04/2024 25 0
ST002 AREA C TANK A 0 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
V009
STORAGE TANK LID
LACKS A
FUNCTIONING
GASKET BETWEEN
THE LID AND FRAME
SIG Gaskets are deteriorating and need replaced 06/04/2024 25 0
TP001 SPRING NO 1 HYPOCHLORINATOR A 75 Hide Details ( 2 )
Code Description Severity Comments Determined
Date Pending Assessed
TD25
DISINFECTION IS
REQUIRED BUT
DISINFECTION IS
INTERMITTENT OR
NOT CONTINUOUS
SIG 01/31/2024 0 50
TD22
LACKS BACKUP
POWER SUPPLY FOR
REQUIRED
DISINFECTION
SIG 01/31/2024 0 25
TP002 UPPER SPRING CHLORINATOR I 0 Hide Details ( 2 )
Code Description Severity Comments Determined
Date Pending Assessed
TD25
DISINFECTION IS
REQUIRED BUT
DISINFECTION IS
INTERMITTENT OR
NOT CONTINUOUS
SIG 01/31/2024 50
TD22
LACKS BACKUP
POWER SUPPLY FOR
REQUIRED
DISINFECTION
SIG 01/31/2024 25
WS001 SPRING #1 (LOWER)A 15 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
SS02 SPRING COLLECTION
AREA NOT FENCED MIN System is still searching for proof of an exception.10/17/2018 0 15
WS002 SPRING #2 (UPPER)I 0 Hide Details ( 3 )
PHYSICAL FACILITY POINTS Total Pts: 90
Facility Facility Name Status Points Effective Details
Code Description Severity Comments Determined
Date Pending Assessed
S001 UNAPPROVED
SOURCE IN SERVICE SIG Unapproved source until primary disinfection is installed
and operational.01/31/2024 200
D009
WATER MAINS
SUSCEPTIBLE TO
NEARBY
CONTAMINATION
SOURCES
SIG
Upper spring line which connects to Pressure Irrigation
after its connection to the Culinary Chlorinator should be
air gapped as it shows it on Engineer stamped plans . This
line is currently Turned out and Inactive to the Culinary
System.
06/04/2024 50 0
D016
DIST SYS LINE
CONNECTED TO OR
SUBJECT TO
CONTAMINATION
SIG
Upper spring transmission line from Spring Box to
chlorinator has a drain that is below water in a ditch
,remains open all winter and line is not disinfected at start
up. This line is currently turned out and inactive .
06/04/2024 50 0
SIGNIFICANT DEFICIENCY VIOLATIONS Total Pts: 100
ID Violation Code Deficiency Determined
Points
Effective
TP001
45 FAILURE ADDRESS
DEFICIENCY (GWR)
TD22
LACKS BACKUP POWER SUPPLY FOR REQUIRED
DISINFECTION
07/18/2024 50
TP001
45 FAILURE ADDRESS
DEFICIENCY (GWR)
TD25
DISINFECTION IS REQUIRED BUT DISINFECTION IS
INTERMITTENT OR NOT CONTINUOUS
07/18/2024 50
LEAD COPPER MONITORING AND QUALITY VIOLATIONS Total Pts: 0
Violation No.Period Code Description/Name Points Effective
CHEMICAL MONITORING RULE VIOLATIONS Total Pts: 0
Facility Violation No Period Code Violation Type Analyte Group Determined Seasonality Points Effective
TREATMENT VIOLATIONS Total Pts: 0
Facility Violation No Period Code Violation Type Analyte Group Determined Points Effective
MICROBIAL RULE VIOLATIONS
Date Range Start: 07/01/2022
Total Pts: 25
Determine Date Compliance Period Code Violation Type Return To Compliance Points Effective
07/21/2023 05/01/2023 - 05/31/2023 3A MONITORING, ROUTINE, MAJOR (RTCR)N 25
OPERATOR CERTIFICATION
Type Level Required Highest Certificate
Distribution Dist 2
Treatment
CONSUMER CONFIDENCE REPORT Total Effective Points: 0
Violation No.Period Code Description/Name Points Effective
PUBLIC NOTIFICATION VIOLATIONS Total Pts: 0
Violation No.Date Code Description/Name Points Effective
IPS COMPLIANCE SCHEDULES
Type Required Activities Severity Created Due
Physical deficiency schedule
STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN
THE LID AND FRAME
SIG 07/02/2024 10/30/2024
Physical deficiency schedule
WATER MAINS SUSCEPTIBLE TO NEARBY CONTAMINATION
SOURCES
SIG 07/02/2024 10/30/2024
Physical deficiency schedule DIST SYS LINE CONNECTED TO OR SUBJECT TO CONTAMINATION SIG 07/02/2024 10/30/2024
Physical deficiency schedule
STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN
THE LID AND FRAME
SIG 07/02/2024 10/30/2024
GROUND WATER REQUIRED TO
DISINFECT
GWR CORRECT DEFICIENCY 120 DAYS SIG 02/01/2024 05/31/2024
GROUND WATER REQUIRED TO
DISINFECT
GWR CORRECT DEFICIENCY 120 DAYS SIG 02/01/2024 05/31/2024
GROUND WATER REQUIRED TO
DISINFECT
GWR CORRECT DEFICIENCY 120 DAYS SIG 02/01/2024 05/31/2024
GROUND WATER REQUIRED TO
DISINFECT
GWR CORRECT DEFICIENCY 30 DAYS SIG 02/01/2024 05/01/2024
GROUND WATER REQUIRED TO
DISINFECT
NOTIFY THE DIVISION 02/01/2024 03/02/2024
GROUND WATER REQUIRED TO
DISINFECT
GWR CORRECT DEFICIENCY 120 DAYS SIG 02/01/2024 05/31/2024
Revised Total Coliform Rule LVL1 TTT TC+/EC- WO RPTS 05/16/2022 06/15/2022