HomeMy WebLinkAboutDDW-2024-009098Sanitary Survey - Deficiency Report
PWS Number:UTAH09084 Deficiency Points:240 Survey Date:06/19/2024
Survey Name:JNB MARINE Surveyor:Ryan Dearing
Sanitary Survey Category: SM
SDWIS Severity Code: Significant Deficiency
Management and Operations | DS001 | UTAH09084 DISTRIBUTION SYSTEM
23. There are no undocumented drinking water facilities (i.e. tanks, pump stations, treatment facilities, etc.) or recent modifications that have not
gone through or in process of DDW review [LIST UNDOCUMENTED FACILITIES OR DESCRIBE MODIFICATIONS, IF APPLICABLE]
[undocumented sources are covered in a different question]
Rule: R309-100-5(2), R309-500-6, R309-500-9,
R309-500-9(2) and (3)
Rule requires complete plans & specification for all public drinking water projects to
be approved in writing by the Director. Any facility found that has not started DDW
review shall be considered unapproved. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:5000 gallon stoarage tank was not on the inventory and does not have plan approval or
operating permit.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: G001 UNAPPROVED FACILITY IN SERVICE
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS001 | STORE WELL
58. Wellhead is sealed to prevent contamination.
Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and
maintained at the wellhead and discharge piping. This significant deficiency should be
corrected within 120 days of notification or have a corrective action plan approved by
Notes:Bolts were removed and top cap was loose.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | HOMES STORAGE TANK
92. Tank is vented.
Rule: R309-545-15 Rule requires drinking water storage tanks to be vented. Overflows cannot be
considered or used as vents. This significant deficiency must be corrected within 120
days of notification or have a corrective action plan approved by DDW.
Notes:There is no vent.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: VL02 STORAGE TANK LACKS AN AIR VENT
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST002 | HOMES STORAGE TANK
94A. Access opening framed at least 4 inches above roof surface or 18 inches above earthen cover.
Rule: R309-545-14(1)Rule requires tank access opening to be framed at least 4 inches above the surface of
the roof, or on a buried tank, to be at least 18 inches above any earthen cover over the
tank.
Notes:Lid is flush with the top of the tank.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V008 TANK ACCESS HEIGHT LESS THAN 4 INCHES ABOVE TANK ROOF OR LESS
THAN 18 INCHES ABOVE EARTHEN COVER
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | HOMES STORAGE TANK
94B. Access opening shoe box type with at least 2 inches of overlap
Rule: R309-545-14(2)Rule requires the frame of an access opening to be provided with a close fitting solid
shoebox type cover which extends down around the frame at least two inches and is
furnished with a gasket(s) between the lid and frame. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:Lid is not shoe box type.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V010 STORAGE TANK LID NOT SHOEBOX STYLE
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | HOMES STORAGE TANK
94C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:There is no gasket.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | HOMES STORAGE TANK
95. Access opening locked
Rule: R309-545-14(3)Rule requires the lid to any access opening to have a locking device. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Lid is not locked.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V029 STORAGE TANK ACCESS OPENING LACKS A LOCK
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | HOMES STORAGE TANK
100. Is a tank overflow present? ... if yes, answer the following question(s)
Rule: R309-545-13 Rule requires all storage tanks to be provided with an overflow that discharges at an an
elevation between 12 and 24 inches above the ground surface or the rim of the receiving
basin. This significant deficiency must be corrected within 120 days of notification or
have a corrective action plan approved by DDW.
Notes:No overflow.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: VL01 STORAGE TANK LACKS AN OVERFLOW