HomeMy WebLinkAboutDDW-2024-009087Sanitary Survey - Deficiency Report PWS Number:UTAH26033 Deficiency Points:20 Survey Date:07/18/2024 Survey Name:DEER CREEK PARK Surveyor:Colt Smith Sanitary Survey Category: SM SDWIS Severity Code: Recommendation Management and Operations | DS001 | UTAH26033 DISTRIBUTION SYSTEM 31. Does your water system have an Emergency Response Plan? Rule: R309-105-18 All suppliers are advised to develop contingency plans to cope with possible emergency situations. In many areas of the state the possibility of earthquake damage shall be realistically considered. Notes:The system does not have an emergency response plan. Deficiency Points: 0 Days until points become effective on IPS: 0 SDWIS Deficiency Description: M001 NO CURRENT EMERGENCY RESPONSE PROGRAM Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | CRESS SPRING 55. Area of equal or higher elevation within 50 feet of spring collection devices is fenced. Rule: R309-515-7(7)(e)Rule requires a stock-tight fence around the spring collection area. Notes:System has an exception Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: SS02 SPRING COLLECTION AREA NOT FENCED Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Springs | WS001 | CRESS SPRING 63. Is a spring collection box present? ... if yes, answer the following question(s) Rule: R309-515-7(7)(c)Rule requires each spring collection area to be provided with at least one collection box to permit spring inspection and testing. Notes: Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: L014 SPRING COLLECTION BOX NOT PRESENT