PWS Number:UTAH21050 Deficiency Points:40 Survey Date:07/17/2024
Survey Name:LIZARD BENCH WATER
ASSOCIATION
Surveyor:John Chartier
Sanitary Survey Category: SM
SDWIS Severity Code: Recommendation
Management and Operations | DS001 | UTAH21050 DISTRIBUTION SYSTEM
31. Does your water system have an Emergency Response Plan?
Rule: R309-105-18 All suppliers are advised to develop contingency plans to cope with possible emergency
situations. In many areas of the state the possibility of earthquake damage shall be
realistically considered.
Notes:No Emergency Response Plan
Deficiency Points: 0
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M001 NO CURRENT EMERGENCY RESPONSE PROGRAM
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | LIZARD BENCH TANK
85A. Mild deterioration or spalling?
Rule: R309-545-6(1) and 545-9(1)Rule requires all water storage tanks to have suitable watertight roofs and sidewalls
that shall also exclude birds, animals, insects, and excessive dust.
Notes:Southwest corner of tank has mild deterioration.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V021 STORAGE TANK ROOF OR SIDEWALLS SHOW SIGNS OF MILD OR MODERATE
DETERIORATION
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | LIZARD BENCH TANK
87A. Drain line shall terminate at least 12 inches above ground or flood rim of receiving basin
Rule: R309-545-10(1)(d)If the local authority allows discharge to a storm drain, the rule requires the drain
discharge to have a physical clearance of at least 12 inches between the discharge end of
the pipe and the overflow rim of the receiving basin. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Drain line needs to have the discharge end uncovered and air gap provided.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V016 END OF TANK DRAIN LINE LACKS A CLEARANCE OF AT LEAST 12 INCHES