HomeMy WebLinkAboutDDW-2024-008943Sanitary Survey - Deficiency Report PWS Number:UTAH26011 Deficiency Points:15 Survey Date:07/12/2024 Survey Name:SNAKE CREEK MUTUAL WATER Surveyor:Melissa Noble Sanitary Survey Category: FW SDWIS Severity Code: Minor Deficiency Management and Operations | DS001 | UTAH26011 DISTRIBUTION SYSTEM 29A. System lacks required storage capacity due to fire demand Rule: R309-510-8(1)(b)Rule requires a public water system to provide equalization storage volume (to meet average day demands for indoor and irrigation water use), fire flow storage volume (if equipped with fire hydrants for fire suppression or required by the local fire code official), and emergency storage (if deemed appropriate by the water system or the Director). Notes:Fire authority says they will not bring a truck up to this system due to lack of space. Deficiency Points: 15 Days until points become effective on IPS: 0 SDWIS Deficiency Description: VF34 SYSTEM LACKS REQUIRED STORAGE CAPACITY DUE TO FIRE DEMAND BUT HAS SOP FOR FOLLOWING FIRE INCIDENT