HomeMy WebLinkAboutDDW-2024-008893Sanitary Survey - Deficiency Report
PWS Number:UTAH28003 Deficiency Points:105 Survey Date:06/18/2024
Survey Name:HANKSVILLE TOWN WATER
SYSTEM
Surveyor:Ryan Dearing
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH28003 DISTRIBUTION SYSTEM
35. Does the water system have detailed records of cross connection control activities? (inventories of backflow assemblies, devices, and air gaps
installed within the system)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes written records of cross connection control activities.
Notes:Need to keep a log of cross connection activities.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M006 CCC-LACKS WRITTEN RECORDS OF CCC ACTIVITIES
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH28003 DISTRIBUTION SYSTEM
36. Does the water system have records of on-going enforcement activities? (test history, enforcement activities, hazard assessments)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes test history and documentation of on-going enforcement activities.
Notes:Need to keep a log of cross connection activities.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M007 CCC-LACKS ON-GOING ENFORCEMENT IMPLEMENTATION
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH28003 DISTRIBUTION SYSTEM
41A. Open end of vent line covered with #14 mesh screen
Rule: R309-550-6(6)(b)Rule states the open end of the air relief vent pipe from automatic valves shall be
provided with a #14 mesh, non-corrodible screen and a downward elbow, and where
possible, be extended to at least one foot above grade. This significant deficiency must
be corrected within 120 days of notification or have a corrective action plan approved
by DDW.
Notes:Air/vac at the Well #3 was not screened properly.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D004 AIR RELIEF VALVE PIPE LACKS NO. 14 SCREEN
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS002 | 1991 WELL
89A. Air vacuum relief valve on well discharge piping downturned
Rule: R309-515-6(12)(d)(v)Rule requires the exhaust/relief piping on an air release/vacuum relief valve on the well
discharge piping to be down-turned. This significant deficiency must be corrected
within 120 days of notification or have a corrective action plan approved by DDW.
Notes:Mushroom cap needs to be removed.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S028 AIR RELEASE VACUUM RELIEF VALVE PIPING NOT DOWNTURNED
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Wells | WS002 | 1991 WELL
89B. Air vacuum relief valve on well discharge piping screened with #14 mesh screen
Rule: R309-515-6(12)(d)(v)Rule requires the exhaust/relief piping on an air release/vacuum relief valve on the well
discharge piping to be covered with a #14 mesh corrosion-resistant screen. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:Mushroom cap needs to be removed and #14 mesh screen added.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S029 END OF AIR RELEASE VACUUM RELIEF VALVE PIPING LACKS NO. 14 SCREEN