HomeMy WebLinkAboutDERR-2024-008866
Meeting UST Compliance Performance Measures
Guide For Inspectors
April 2018
This document provides underground storage tank (UST) inspectors with information to use in
determining whether facilities meet the UST compliance performance measures. This document
will also help inspectors calculate EPA’s technical compliance rate. Individual implementing
agencies may choose to modify this document to ensure it meets your state’s requirements and
inspection procedures. The federal UST regulation requires UST owners and operators to
comply with several periodic requirements. Examples include spill prevention equipment and
containment sumps used for interstitial monitoring of piping are required to be tested at least
once every three years. Owners and operators must perform periodic requirements on or before
the same day of the period after the previous requirement was performed.
These resources can help inspectors prepare for and conduct inspections.
• Federal UST regulation https://www.epa.gov/ust/revising-underground-storage-tank-
regulations-revisions-existing-requirements-and-new
• States with updated regulations that incorporate 2015 federal UST regulation
https://www.epa.gov/ust/state-underground-storage-tank-ust-programs#2015update
• EPA’s UST publications https://www.epa.gov/ust/publications-related-underground-storage-
tanks
• National Work Group On Leak Detection Evaluations’ (NWGLDE) List Of Leak Detection
Evaluations For Storage Tank Systems http://www.nwglde.org/
• Underground Storage Tank Technical Compendium about the 2015 UST Regulation –
https://www.epa.gov/ust/underground-storage-tank-ust-technical-compendium-about-2015-
ust-regulations
Contents
Page
UST Compliance Performance Measures Included in the Technical Compliance Rate
UST-9a. Spill Prevention 2
UST-9b. Overfill Prevention 2
UST-9c. Corrosion Protection 3
UST-9d. Release Detection 5
Technical Compliance Rate
UST-9e. Combined Measure: Technical Compliance Rate 10
UST Compliance Performance Measures Not Included in the Technical Compliance Rate
UST-10. Operator Training 11
UST-11. Financial Responsibility 11
UST-12. Walkthrough Inspections 11
For More Information 12
2
UST Compliance Performance Measures Included In The
Technical Compliance Rate
UST-9a. Spill Prevention
Spill prevention is not required for USTs in proper temporary closure or for USTs that never
receive deliveries >25 gallons.
Element a: Spill prevention device is present and functional. [280.20(c)(1)(i), 280.21(d)]
Verify that:
• Spill bucket is present.
• Spill bucket does not have any holes or cracks.
• In your judgment, the spill bucket will catch or contain drips or spills when the delivery hose
is disconnected from the fill pipe.
Element b: Spill prevention device is tested every 3 years or periodically monitored.
[280.35(a)(1)]
Verify that:
• Spill prevention equipment was tested in last 3 years and passed.
• If spill prevention failed test, it was repaired, retested and passed or replaced, according to a
code of practice.
• Records for the last 3 years exist.
• Documentation of double-wall and periodic monitoring, if monitoring integrity of both walls
every 30 days instead of testing every 3 years. Records must be maintained for as long as the
spill bucket or containment sump is using periodic monitoring of the interstitial space.
UST-9b. Overfill Prevention
Overfill prevention is not required for USTs in proper temporary closure or for USTs that never
receive deliveries >25 gallons.
Element a: Overfill prevention device is present and operational. [280.20(c)(1)(ii), 280.21(d)]
• Flapper valve is operational, that is, device is not tampered with or inoperable.
[280.20(c)(1)(ii)(A), 280.21(d)]
• High level alarm is operational and audible or visible to delivery driver. [280.20(c)(1)
(ii)(B), 280.21(d), 280.20(c)(1) (ii)(B), 280.21(d)]
• Ball float is operational. [280.20(c)(1)(ii)(B), 280.21(d)]
Identify the overfill prevention method used:
• Flapper valve automatically shuts off delivery when the tank is 95% full or before fittings on
top of the tank are exposed to fuel.
o Verify presence by installation records, contractor verification, or field observation.
o Verify the flapper valve has not been tampered with, for example using a stick in the drop
tube, to inhibit or modify the shut-off point.
o Perform a visual observation of flapper valve housing in the fill pipe to look for damage.
3
• High level alarm, either audible or visible, sounds when tank is 90% full or 1 minute before
being overfilled.
o Test or observe the owner or operator test the alarm to verify it is functional.
o Driver can see or hear alarm, as applicable, at point of transfer.
• Ball float valve restricts product flow when tank is 90% full or 30 minutes before being
overfilled.
o If possible, verify presence by records or field observations. If not possible, require
owner or operator obtain certification, for example from the contractor, that the ball float
valve is present.
o Accessible fittings, for example the spill bucket drain mechanisms, are sealed and intact
so that the top of the tank is tight.
o Verify that appropriate device is being used; for example, ball float valves are
inappropriate with some Stage I vapor recovery systems and suction piping systems.
o If the ball float valve is not operating properly and cannot be repaired, the overfill device
must be replaced with either an automatic shutoff device or overfill alarm.
Element b: Overfill prevention device is inspected every 3 years. [280.35(a)(2)]
Compare delivery record’s quantities to ullage at time of product delivery. If there is evidence of
a problem, check if the UST was ever filled beyond its capacity; this may indicate the overfill
device is not working. Verify that:
• The overfill was inspected within the last 3 years.
• If overfill failed, it was repaired, retested and passed, or replaced according to code of
practice. A ball float cannot be replaced with another ball float.
• Records for last 3 years exist.
UST-9c. Corrosion Protection
Element a: Metal tank and piping, which includes fittings, connections, etc., are protected from
corrosion. [280.20(a), 280.20(b), 280.21(b), 280.21(c)] Metal piping components, such as
swing joints, flex-connectors, etc., are isolated from the ground or cathodically protected.
Fiberglass reinforced plastic (FRP) tanks and piping satisfy the corrosion protection (CP)
requirements. Regardless, verify that metal components are isolated or booted, cathodically
protected, or not in contact with the ground.
Verify records are available to document either:
• Tank, piping, and all fittings or connections are protected against corrosion; or
• CP is not necessary.
Element b: CP systems were tested or inspected, as applicable, within 6 months of repair of any
cathodically protected UST system. [280.33(e)]
Element c: Corrosion protection system is properly operated and maintained to provide
continuous protection. [280.31(a)(b), 280.70(a)]
• CP system is properly operated and maintained; this includes USTs in temporary closure.
o CP system is performing adequately based on results of testing. [280.31(b)]; or
4
o CP system tested within required period and operator is conducting or has completed
appropriate repair in response to test results reflecting CP system not providing
adequate protection.
Element d: UST systems with impressed current cathodic protection are inspected every 60
days to ensure equipment is running properly. [280.31(c)]
Operation And Maintenance of Corrosion Protection
Corrosion protection must be maintained on USTs in temporary closure. This includes recording
rectifier readings and performing the periodic CP test and internal lining inspections, as
applicable.
For each UST system, identify:
• Installation date of UST system;
• Corrosion protection method used;
• Type of material used to construct tank, line, and other components in contact with the
ground; and
• Date of repairs to tanks, lines, and other components in contact with the ground.
• Cathodic protection – impressed current, verify that:
o The rectifier is operational.
o Rectifier’s electrical source provides power 24 hours a day, every day. Check for
dedicated power source.
o Records are available for two of the last three 60-day inspections; ensure there is a
rectifier reading and it was performed within the last 60 days. The most recent inspection
must show that the rectifier is operating within normal limits and all indications are that
the CP system has not been turned off.
o The rectifier has been operating continuously. Use the meter, if present and operational,
to determine if rectifier has been turned off or without power. You can use the previous
reading to calculate a reasonable estimate of what the meter hours should be.
o CP system was tested within the last 3 years.
o The most recent CP system test showed corrosion protection was adequate, for example,
it meets -850 mV instant off or 100 mV polarization criterion, and that any non-passing
results were promptly investigated and corrected to achieve a passing result.
o When looking at tightness test records, tanks and piping were tightness tested within 30
days of repair completion; this is not required for tank and piping using monthly
monitoring.
o CP system was tested within 6 months of repair to the CP system.
o Metal components at tank and dispenser are isolated, or booted, cathodically protected, or
not in contact with the ground.
• Cathodic protection – galvanic with sacrificial anodes, verify that:
o The most recent CP system test showed corrosion protection was adequate, or -850 mV,
and that non-passing results were promptly investigated and corrected to achieve a
passing result.
5
o When looking at tightness test records, tanks and piping were tightness tested within 30
days of repair completion; this is not required for tanks using monthly monitoring.
o CP systems were tested within 6 months of repair to the CP system.
Element e: Lined tanks are inspected periodically and lining is in compliance.
[280.21(b)(1)(ii)] According to date established by the implementing agency, owners and
operators must permanently close, per subpart G, an UST system that does not meet the new
UST system performance standards in 280.20 or has not been upgraded or lined as required.
• Internal lining, applies to tanks only, verify that:
o Internal lining was inspected in a timely manner, meaning within 10 years after
installation and every 5 years thereafter.
o Internal lining was inspected by a procedure acceptable to implementing agencies, some
of whom do not accept inspection by video camera.
o Tank passed the internal lining inspection or one of the following was done, per API
1631:
Lining repaired;
Cathodic protection system installed, if tank’s metal thickness is ≥ 75% original
thickness; or
Tank permanently closed.
o If lining could not be repaired, tank was permanently closed.
UST-9d. Release Detection
This information generally applies:
• For purposes of EPA release detection requirements, the portion of the tank that routinely
contains product does not typically include vent pipes; fill pipes, including remote fill pipes;
and fittings on top of the tank, as long as the UST system is in compliance with overfill
prevention requirements.
• If documentation regarding release detection equipment is not on site, possible sources of
information are:
o NWGLDE
o Equipment manufacturer
• For containment sump testing, owners only have to test if they are using the containment
sump for release detection.
• For UST systems in temporary closure, verify that UST systems containing product comply
with release detection requirements.
o Release detection equipment testing is not required as long as the UST system is empty.
[(280.70(a)]
• For hazardous substance UST systems, where applicable, look for interstitial monitoring for
both piping and tank.
o Secondary containment with interstitial monitoring for all hazardous substance USTs,
there is no variance to use other methods, according to date established by the
implementing agency.
6
Release Detection Method Presence And Performance Requirements
Element a: Determine that appropriate release detection is: present, operating properly, meets
specific performance standards.
•Appropriate release detection method is present. [280.40(a)]
o Appropriate use of release detection equipment depends on relevant compliance deadlines
established by the implementing agency, such as its requirement for secondary
containment with interstitial monitoring.
•Release detection equipment is operational, meaning it is able to detect a release from any
portion of the system that routinely contains product. [(280.40(a)(1)]
•Release detection system meets specific performance standards in §§ 280.43 or 280.44, or
subpart K. [(280.40(a)(3)]
•UST systems containing product and in temporary closure comply with release detection
requirements. [280.70(a)]
o Release detection equipment testing is not required as long as the UST system is empty.
[(280.70(a)]
•Hazardous substance UST systems meet release detection secondary containment
requirements or, for older USTs, are otherwise approved by the implementing agency.
[280.42(a) and 280.42(e)]
•Verify an appropriate release detection method is being used as allowed by implementing
agency’s compliance dates. Some, but not all key concerns are listed by individual release
detection method below.
•Inventory control – to check that inventory control is being properly performed, review
records for improper recording, data collection, and reconciliation activities.
o Collect inventory data for all days the facility was in operation, either dispensing or
conducting deliveries.
o Height to volume should be properly translated.
o Height data should show approximately 50% of measurements using 1/8-inch increments.
o Check the stick for proper length, proper increments, and good condition. Stick should be
unbroken and include the button, or its bottom portion.
o Check that proper tank conversion chart is being used; chart must be appropriate to the
size of the tank used.
o Ensure the facility is not using inventory control with tank tightness testing beyond the
10-year deadline established by the implementing agency.
•Automatic tank gauging – these verification procedures apply to the automatic tank gauging
(ATG) system used in static test mode and as continuous in-tank leak detection (CITLD).
o To determine proper setup, check the report of the leak detection test to determine that:
Leak rate is appropriate.
Correct tank size is programmed into ATG.
o Check the report of the leak detection test to determine it adheres to specifications listed
by sources such as NWGLDE:
Test period sufficient.
Test capacity appropriate, for example at least 50% full.
7
Size of tank meets equipment limitations.
o Determine the level of product in the tank at the time of test to ensure that it is close to
the normal high in the tank as determined from the inventory monitoring records.
Be aware that unless you are properly trained, tampering with the ATG is not
recommended. Regardless of training, exercise care so you don’t inadvertently
reprogram or negatively affect the ATG’s operation.
o These additional verification procedures are specific to ATGs used for CITLD and apply
to both subcategories of continuous automatic tank gauging and continual reconciliation.
Check that ATG is running acceptable software enabling release detection testing on
an uninterrupted basis or operating within a process that allows the system to gather
incremental measurements to determine a leak.
Ensure pass or fail result within 30-day period. Inconclusive result means release
detection requirement not met.
•Manual tank gauging
o Check the stick for proper length, proper increments, and good condition. Stick should
be unbroken and include the button. Reference EPA’s publication on manual tank
gauging https://www.epa.gov/ust/manual-tank-gauging-small-underground-storage-tanks.
•Tightness testing
o Check the report to determine it adheres to specifications listed by sources such as
NWGLDE.
•Groundwater and vapor monitoring
o Site assessment is available for life of method use and signed by P.E., P.G., or equivalent,
according to date established by the implementing agency.
Verify site assessment is available and shows wells properly placed and constructed.
Ensure layout of the monitoring wells would detect a release from any portion of the
tank system.
o Check inside of monitoring well to determine if well is appropriately screened.
Check to see if well is screened at proper depth for groundwater monitoring. Proper
depth is site specific.
Water level should be below screening to allow enough headspace for product phase
change.
•Interstitial monitoring of tank and piping
o Visually inspect, if accessible. Look for obvious degradation of the tank top sump, or
piping interstice, and for water intrusion into the tank interstice or the tank top sump.
o Ensure the float sensor, if used, is installed correctly per manufacturer’s instructions; it is
typically vertical and at the bottom of the sump. Sensor should be raised to an acceptable
level, but not beyond.
Verifying sensor position does not require removing the UST system sensors.
o The presence of water indicates a problem. At best, the water is from surface run-off,
which still shows that the secondary containment system is not tight enough to prohibit
water intrusion. At worst, water indicates there is a breech allowing groundwater
intrusion.
8
If the presence of water renders the release detection method inoperable so that a
release could go undetected for more than 30 days, the compliance measure is not
met.
o Ensure interstitial monitoring is primary release detection method according to secondary
containment with interstitial monitoring requirement date established by the
implementing agency.
• Statistical inventory reconciliation – check report to determine that sufficient amount of data
was used to perform leak check.
o Ensure only quantitative methods are used according to date established by
implementing agency. Qualitative methods with simply an indication of pass or fail are
unacceptable.
o Inventory data can be obtained manually with gauge stick or from ATG.
o Report must indicate leak rate threshold based on data analyzed and cannot exceed one-
half the minimum detectable leak rate.
o Data collection, data delivery to vendor, analysis, and receipt of report determining pass
or fail leak status are required within 30-day monitoring period.
• Automatic line leak detectors on pressurized piping – visually verify presence of automatic
line leak detector (ALLD) or obtain written proof or affidavit from contractor that ALLD is
present.
o During visual inspection, look for either a mechanical line leak detector (MLLD) on the
submersible pump head or an electronic line leak detector (ELLD) located anywhere in
line.
o ELLD will also have a console inside the office. When looking at the console, check to
ensure there is an ELLD connected and tests are performed. If there is no visual
evidence of leak detection equipment, look for the annual operability test report.
o Ensure the ALLD is situated so that the entire piping system is covered.
o Ensure the MLLD is product appropriate where necessary, for example, diesel Red
Jacket FX series on a diesel system.
o Ensure ALLD with interstitial monitoring for piping is the primary method of release
detection because annual line tightness test with just ALLD is no longer allowed per
date of secondary containment with interstitial monitoring established by the
implementing agency.
Performing Release Detection Monitoring And Recordkeeping
Element b: Tanks and piping are monitored monthly or a periodic line tightness test is
performed for releases, and owners must have available the records for the two most recent
consecutive months and for 10 of the last 12 months. [280.41(a) & (b) and 280.45(b)]
• Crosscheck walkthrough inspections records to ensure records of release detection testing,
including monthly monitoring, are reviewed.
• Obtain previous records from facility.
• Search ATG memory as applicable.
9
Element c: Electronic and mechanical release detection equipment are tested at least annually
for proper operation and records are maintained for 3 years. [280.40(a)(3) and 280.45(b)(1)]
• Equipment includes ATG and other release detection system controllers, probes, sensors,
ALLD, vacuum pumps, pressure gauges, and hand-held electronic sampling.
• Ensure test has been conducted within the last year according to requirements developed by
the equipment manufacturer, a code of practice such as Petroleum Equipment Institute (PEI)
RP 1200, or implementing agency requirements.
• Ensure records for current test and the two previous tests, or three total tests if counting
current, are available. For ALLD test, ensure leak simulation to verify performance standard
of 3 gallons per hour at 10 pounds per square inch line pressure within 1 hour is met.
Element d: Containment sumps used for interstitial monitoring of piping are tested at least
every 3 years. [280.35]
• Ensure test has been conducted within the last 3 years according to requirements developed
by the sump manufacturer, a code of practice such as Petroleum Equipment Institute (PEI)
RP 1200, or implementing agency requirements.
• Review records.
• If monitoring integrity of both walls at least annually instead of testing every 3 years, then
verify documentation of double wall and periodic monitoring.
Element e: Implementing agency has been notified of suspected release as required.
[(280.40(b)]
• Non-passing results reported and resolved according to implementing agency’s directions.
[280.40(b)]
• Check indications of past or current suspected releases, such as ATG console alarm history
with implementing agency records.
10
Technical Compliance Rate
UST-9e. Combined Measure: Technical Compliance Rate
Determine the technical compliance rate by looking at the spill prevention, overfill prevention,
corrosion protection, and release detection measures. In order to be in compliance with the
combined measure, the facility must be in compliance with UST measures 9a-9d.
11
UST Compliance Performance Measures Not Included In The
Technical Compliance Rate
For each UST measure, remember to count compliance at the facility.
UST-10. Operator Training
Ensure Class A and B operators are properly trained.
• Class A and B operators properly complete initial training. [280.240 – 280.243]
• Class A and B operators are properly re-trained. [280.244]
• Documentation of training is available. [280.245]
• Verify Class A and B operators were trained.
• Verify records are properly maintained, including through databases.
UST-11. Financial Responsibility
• Verify owner or operator demonstrates financial responsibility (FR).
• Verify wording in FR documents has not been altered from the required language in the FR
regulation, per subpart H.
• Verify owner’s FR includes both third party liability and cleanup coverage; ensure that
coverage is the correct amount.
o Some state funds may not provide third party liability coverage and may not provide
required first dollar coverage for a deductible. Insurance policies may be written to
provide only third party, only cleanup coverage, or both.
• Verify all USTs on site or registered with the implementing agency are included on the FR
documents.
• For insurance, verify that the policy provides required first dollar coverage and there is no
self-insured retention. A policy with self-insured retention is only a partial FR mechanism.
• This measure is unique in that the implementing agency can verify if a facility complies with
FR at the time the implementing agency determines compliance with FR, rather than at the
time of a facility inspection. Some implementing agencies do not determine compliance with
FR during the inspection.
• FR must still be determined based on the initial document reviewed, either at the time of
submission of FR information to the implementing agency or the time of inspection. If the
implementing agency works with an owner to come into compliance after the initial
submission, the facility is not in compliance with the FR measure.
UST-12. Walkthrough Inspections
• Ensure system is operating properly by conducting applicable monthly and annual
walkthrough inspections. [280.36(a)]
o Conduct monthly walkthrough inspection according to federal UST regulation.
[280.36(a)]
12
o Maintain records of operation and maintenance monthly walkthrough inspections; owners
must have records for the two most recent consecutive months and for 10 of the last 12
months. [280.36(b)].
o Conduct annual walkthrough inspection according to federal UST regulation. [280.36(a)]
o Maintain records of operation and maintenance annual walkthrough inspections; owners
must have record of last inspection. [280.36(b)].
• Verify a walkthrough inspection was conducted every 30 days that, at a minimum, checked
the equipment listed below. Exception to every 30 days: spill prevention equipment at UST
systems receiving deliveries at intervals greater than every 30 days may be checked prior to
each delivery.
o Spill prevention equipment – visually check for damage; remove liquid or debris; check
for and remove obstructions in the fill pipe; check the fill cap to make sure it is securely
on the fill pipe; and, for double-walled spill prevention equipment with interstitial
monitoring, check for a leak in the interstitial area.
o Release detection equipment – check to make sure the release detection equipment is
operating with no alarms or other unusual operating conditions present; and ensure
records of release detection testing, which includes monthly monitoring, are reviewed
and current.
o Walkthrough conducted according to a standard code of practice developed by a
nationally recognized association or independent testing laboratory such as PEI PR 900.
• Verify at least 10 months of records are maintained for one year. If spill buckets are checked
less than once a month, verify records of deliveries.
• Verify owner conducted a walkthrough inspection annually that, at a minimum, checked the
equipment listed below.
o Sumps – visually check for damage, leaks to the containment area, or releases to the
environment; remove liquid in contained sumps or debris; and, for double-walled sumps
with interstitial monitoring, check for a leak in the interstitial area.
o Hand held release detection equipment – check devices such as tank gauge sticks or
groundwater bailers for operability and serviceability.
o Walkthrough conducted according to a standard code of practice developed by a
nationally recognized association or independent testing laboratory such as PEI PR 900.
• Verify records are maintained for one year.
For More Information
Contact Liz McDermott of EPA OUST (202-564-0646; mcdermott.elizabeth@epa.gov).