HomeMy WebLinkAboutDDW-2024-008732July 8, 2024
Via Email: rjohnson@wcwid.org
Paul Ashton
White City Water Improvement District
999 East Galena Drive
Sandy, Utah 84094
Subject:2024System-SpecificMinimum Sizing Standards—Final Determination
White City Water Improvement District, System #18019, File #11578
Dear Paul Ashton:
DETERMINATIONS
Based on the findings set forth below, the Division of Drinking Water (the Division) hereby establishes the following system-specific minimum sizing standards for White City Water Improvement
District (the System):
Peak Day Source Demand (gallons/day/ERC) – 1,510
Average Annual Demand (gallons/year/ERC) – 205,377
Equalization Storage (gallons/ERC) – 563
Fire Storage (gallons) – 675,000
Introduction
Pursuant to Utah Code Section 19-4-114, the Director of the Division (Director) is required to establish system-specific minimum sizing standards based on, among other factors, water
use data submitted to the Division of Water Rights (DWRi). The Director’s determinations may also be based on engineering analyses and other evidence if this is available. This final
determination letter is addressed to you in your capacity as the Administrative Contact for the System. The Director has delegated the responsibility for making system-specific minimum
sizing standards under Utah Code Section 19-4-114 to the Engineering Manager for the Division.Prior to issuing this final determination letter, the Division analyzed applicable DWRi
water use data and sent a draft summary of the Division’s proposed system-specific minimum sizing standards to the System on March 25, 2024. A summary of the water use data and calculations
the Division used to make these determinations is attached as part of the administrative record.
Water Use Data Definitions
As used in this Final Determination, the following terms have the following meanings:
Peak Day Source Demand is the total flow into a public water system to meet the demand of the water system on the day of the highest water consumption in a calendar year.
Average Annual Demandis the total quantity of drinking water flowing into a public water system within a calendar year.
Total Equivalent Residential Connections (ERCs) term represents the number of residential service connections and the number of equivalent residential connections for non-residential
connections (commercial, industrial, institutional connections).
Minimum Equalization Storagerequirement is a volume that is equivalent to the amount of water needed to meet the average day culinary demand for public water systems. Equalized storage
per ERC is calculated by dividing the Average Annual Demand per ERC data by the number of operational days in a year.
Water System Background Facts
White City Water Improvement District is a community water system which serves water for indoor and outdoor use to a population of approximately 15,800 with 5,5051 equivalent residential
connections.System-Specific Minimum Sizing Standards—BackgroundUnder Utah Code Section 19-4-114, the legislature required that the Director establish minimum sizing standards on a system-specific
basis instead of statewide, as the Division has done in the past. System-specific determinations need to be based on system-specific information. The code allows the Director to rely
on water use data submitted to DWRi. Alternatively, a community water system may perform and submit an engineering study to the Division if the water system’s water use data is not representative
of future use or the water system does not yet have actual water use data. In this matter, actual water use data was available through DWRi, and an engineering study was not submitted
to the Division for review. Therefore, the Division has relied upon DWRi information and other relevant data.
Additional System-Specific Basis for Determinations
The Division established fire storage requirements based on information provided by Cliff Linford, P.E. with Sunrise Engineering on September 30, 2020. During the review of water use
data for the 2024 minimum sizing standards, no changes to the fire storage requirements were made by the System. The International Fire Code was used as a reference to determine the
maximum fire suppression requirements for each tank zone in the system and a summary was provided to the Unified Fire Authority and Sandy City Fire Department.
Storage Capacity
Based on the System’s storage facilities and the storage minimum sizing requirement established in this letter, the Director hereby determines that the System is compliantwith the minimum
storage capacity requirements.
Source Capacity
The Division has adequate documentation of established safe yields for all the System’s sources. Using total system-wide safe yields and the source minimum sizing requirement established
in this letter indicates that the System is compliant with minimum source capacity requirements.
Effective Date
The determinations made in this letter are effective immediately and will become final 30 days from the date of this letter unless the System files a contest as provided below.
Notice of Right to Contest
The Director has determined this determination made under Section 19-3-114 qualifies as a “permit order” within the meaning of Utah Code Section 19-1-301.5(1)(f). See Utah Code § 19-1-301.5(1)(e)
(defining “permit” to include a “plan” or “other administrative authorization”).
The System may contest any determinations made herein by delivering a notice of contest to the Director. The notice of contest must be in writing and must be delivered to the Director
on or before 30 days after the date this letter is signed. There is no particular form for the notice of contest, but it must include the System’s reasons and rationale for the contest.
The Director’s address for purposes of submitting a notice of contest is as follows:
U.S. Mail
Division of Drinking Water
Attention: Director
P.O. Box 144830
Salt Lake City, UT 84114-4830
Email
A notice of contest may be submitted to the Director by email, provided, however, that the Director confirms receipt of the email. The Director’s email address is: nlunstad@utah.gov.
The email submission must be received by the Director before the expiration of the contest deadline.
If the System files a timely notice of contest, the Director will evaluate the matter and attempt to resolve the matter through negotiations. If the Director is not able to resolve the
matter, the Director will issue a final agency action regarding the contest. At that point in the process, the System shall have the right to seek further internal agency and judicial
review pursuant to Utah Admin. Code R305-7 and Utah Code Section 19-1-301.5.
Right to Request Reconsideration
The Director plans to evaluate the determinations made herein every three years. However, this requirement is not mandatory. At any time, a water system whose system-specific minimum
sizing standards have been established by the Division under Section 19-4-114 may request reconsideration of the Director’s determinations by submitting a written request. A request
for reconsideration shall be submitted to the Director in the same manner as a notice of contest provided above.
Conclusion
If the Systemmanagement has any questions regarding this letter, please contact Julie Cobleigh, of this office, at (385) 214-9770, or me at (385) 515-1464.
Sincerely,
Michael Newberry, P.E.
Permitting and Engineering Support Manager
JJC/mrn/mdbEnclosuresUtah Department of Environmental Quality Division of Drinking Water Minimum Sizing Standards Summary Reportcc:Mattias Neville, Salt Lake County Health Department,
mrneville@slco.orgPaul Ashton, White City WID, pashton@wcwid.orgJulie Cobleigh, P.E., Division of Drinking Water, jjcobleigh@utah.govClint Mecham, Unified Fire Authority, cmecham@ufa-slco.orgRobert
Dekorver, Sandy City Fire Department, rdekorver@sandy.utah.gov Ted Black, Office of the State Fire Marshal, tblack@utah.govjcobleigh 18019 11578 Standard Set