HomeMy WebLinkAboutDDW-2024-008674Sanitary Survey - Deficiency Report
PWS Number:UTAH17002 Deficiency Points:50 Survey Date:07/01/2024
Survey Name:GARDEN CITY Surveyor:Cameron Draney
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Treatment - General | TP002 | MEMBRANE PLANT
203. Incompatible chemicals stored separately
Rule: R309-525-11(7)(a)(iv)Rule prohibits chemicals that are incompatible from being fed, stored, or handled
together. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Citric acid and caustic soda stored together. Recommended separate spill containment.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TG19 INCOMPATIBLE CHEMICALS ARE FED, STORED OR HANDLED TOGETHER
Sanitary Survey Category: MR
SDWIS Severity Code: Significant Deficiency
Treatment - General | TP002 | MEMBRANE PLANT
204. Daily operating records reflect chemical dosages and total quantities used
Rule: R309-105-14(3)(a)Rule requires all water system using chemical addition or specialized equipment for the
treatment of drinking water to regularly complete operational reports. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:Modifications to SCADA needed to calculate actual dosages.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TG20 DAILY RECORDS DO NOT REFLECT DOSAGES ACCURATELY