HomeMy WebLinkAboutDDW-2024-008659Sanitary Survey - Deficiency Report
PWS Number:UTAH03105 Deficiency Points:180 Survey Date:06/04/2024
Survey Name:CINNAMON CREEK REC
AREA
Surveyor:Brian Pattee
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH03105 DISTRIBUTION SYSTEM
31. Does your water system have an Emergency Response Plan?
Rule: R309-105-7, 8 & 18, R309-100 through
605
Trigger for regulatory followup to address concerns.
Notes:Transient system
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH03105 DISTRIBUTION SYSTEM
40. No unprotected connection between the distribution system and a source of contamination. (If there is an unprotected connection, describe
the location in detail.)
Rule: R309-550-5(11)R309-550-5(11)
Notes:Upper spring line which connects to Pressure Irrigation after its connection to the Culinary
Chlorinator should be air gapped as it shows it on Engineer stamped plans . This line is
currently Turned out and Inactive to the Culinary System.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D009 WATER MAINS SUSCEPTIBLE TO NEARBY CONTAMINATION SOURCES
Sanitary Survey Category: DS
SDWIS Severity Code: Significant Deficiency
Distribution | DS001 | UTAH03105 DISTRIBUTION SYSTEM
44. Blow offs or air release valves do not discharge below flood level in ditches or streams.
Rule: R309-550-9(1) and (2), R309-550-13(2)R309-550-9(1 & 3)
Notes:Upper spring transmission line from Spring Box to chlorinator has a drain that is below
water in a ditch ,remains open all winter and line is not disinfected at start up. This line is
currently turned out and inactive .
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: D016 DIST SYS LINE CONNECTED TO OR SUBJECT TO CONTAMINATION
Sanitary Survey Category: SO
SDWIS Severity Code: Minor Deficiency
Springs | WS001 | SPRING #1 (LOWER)
54. Area of equal or higher elevation within 50 feet of spring collection devices is fenced.
Rule: R309-515-7(7)(e)Rule requires a stock-tight fence around the spring collection area.
Notes:No fence
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: SS02 SPRING COLLECTION AREA NOT FENCED
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | AREA A & B TANK
86C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Gaskets are deteriorating , Need replaced
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST002 | AREA C TANK
100C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Gaskets are deteriorating and need replaced
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME