HomeMy WebLinkAboutDDW-2024-008612Sanitary Survey - Deficiency Report
PWS Number:UTAH14004 Deficiency Points:165 Survey Date:06/19/2024
Survey Name:HINCKLEY TOWN WATER
SYSTEM
Surveyor:Chris Martin
Sanitary Survey Category: TR
SDWIS Severity Code: Minor Deficiency
Management and Operations | DS001 | UTAH14004 DISTRIBUTION SYSTEM
31. Does your water system have an Emergency Response Plan?
Rule: R309-105-7, 8 & 18, R309-100 through
605
Trigger for regulatory followup to address concerns.
Notes:No ERP was provided.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: TGR9 TRIGGER FOR REGULATORY FOLLOWUP TO ADDRESS CONCERNS
Sanitary Survey Category: SM
SDWIS Severity Code: Minor Deficiency
Cross Connection and Operator Certification | DS001 | UTAH14004 DISTRIBUTION SYSTEM
34. Documentation of personnel trained to manage the program (COMMUNITY WATER SYSTEMS POPULATION 500 AND ABOVE
REQUIRE A DDW CERTIFIED CCC PROGRAM ADMINISTRATOR. ALL OTHER WATER SYSTEMS REQUIRE AT A MINIMUM
BACKFLOW 101 OR EQUIVALENT/ GREATER CCC TRAINING)
Rule: R309-105-12(2)Rule requires each public water system to have a cross connection control program
that includes an operator with adequate training in the area of cross connection control
or backflow prevention.
Notes:Water operators do not have a current program admin certification.
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: M005 CCC-LACKS OPERATOR TRAINING
Sanitary Survey Category: OC
SDWIS Severity Code: Significant Deficiency
Cross Connection and Operator Certification | DS001 | UTAH14004 DISTRIBUTION SYSTEM
37. Operator meets required level of certification for water system. ( IF NO CERTIFIED OPERATOR IS REQUIRED MARK COMPLIANT )
Rule: R309-105-11, R309-300-5(3)Rule requires every community and NTNC water system and public water systems that
utilize treatment/filtration to have at least one operator certified at the classified grade
of the water system. Certification must be appropriate for the type of system operated
(treatment and/or distribution). This significant deficiency must be corrected within
120 days of notification or have a corrective action plan approved by DDW.
Notes:No operator has a current distribution certification.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: C001 SYSTEM DIRECT RESPONSIBLE CHARGE OPERATORS NOT CERTIFIED AT THE
REQUIRED LEVEL
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | 400K STORAGE TANK
97D. Vent 6-inch diameter and larger protected with additional heavy-gauge screen or substantial covering.
Rule: R309-545-15(5)Rule requires vents that are 6-inch diameter or greater to be fitted with additional
heavy gauge screen or substantial covering, which will protect the No. 14 mesh screen
against vandalism or damage.
Notes:Deficiency still on IPS report
Deficiency Points: 5
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V035 STORAGE TANK VENT LARGER THAN 6 INCHES IN DIAMETER LACKS
PROTECTIVE SCREEN
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | 400K STORAGE TANK
98C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Needs new gasket
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: FW
SDWIS Severity Code: Minor Deficiency
Storage Tanks | ST001 | 400K STORAGE TANK
102. Storage tank roof is sloped to prevent ponding
Rule: R309-545-9(4)Rule requires drainage of storage tank roofs to eliminate water ponding.
Notes:Same deficiency on IPS report
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: V003 WATER PONDING ON STORAGE TANK ROOF OR TANK ROOF NOT SLOPED TO
DRAIN
Sanitary Survey Category: PU
SDWIS Severity Code: Minor Deficiency
Pump Stations | PF002 | 750 GPM BOOSTER STATION
135. Discharge piping has a pressure gauge.
Rule: R309-540-5 (6)(c)(i)Rule requires that a standard pressure gauge be installed on the pump discharge line.
Notes:Needs a gauge
Deficiency Points: 15
Days until points become effective on IPS: 0
SDWIS Deficiency Description: PS03 PUMP FACILITY LACKS PRESSURE GAUGE ON DISCHARGE LINE
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Gaseous Chlorination | TP003 | ARSENIC PLANT
186. Chlorine cylinder is restrained in position to prevent upset.
Rule: R309-520-7(2)(h)Rule requires chlorine cylinders to be restrained in position to prevent upset. This
significant deficiency must be corrected within 120 days of notification or have a
corrective action plan approved by DDW.
Notes:The cylinder restraints are missing.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD15 CHLORINE CYLINDERS NOT RESTRAINED