Loading...
HomeMy WebLinkAboutDDW-2024-008549Sanitary Survey - Deficiency Report PWS Number:UTAH07006 Deficiency Points:185 Survey Date:06/24/2024 Survey Name:JOHNSON WATER DISTRICT Surveyor:Nathan Hall Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS001 | WELL #1 58. Wellhead is sealed to prevent contamination. Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and maintained at the wellhead and discharge piping. This significant deficiency should be corrected within 120 days of notification or have a corrective action plan approved by Notes:Sounding tube is not sealed Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS001 | WELL #1 60C. Pump to waste line downturned if it discharges to sewer/storm drain or allowing complete drainage if not downturned Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be downturned. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:End of pump to waste line is upturned, with no provision for complete drainage. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S011 WELL PUMP TO WASTE LINE NOT DOWNTURNED Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL #1 66. Well discharge line has a smooth-nosed sampling tap, which samples the well water before any chemical injection. (first item from the wellhead). Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. (smooth nosed sampling tap being the first item from the well head and the shut-off valve as the last item) Notes:There is not a smooth nosed sample tap. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S023 NO SMOOTH NOSED SAMPLING TAP ON DISCHARGE PIPING Sanitary Survey Category: SO SDWIS Severity Code: Minor Deficiency Wells | WS001 | WELL #1 70. Well discharge line has a shut-off valve (last item from the well head). Rule: R309-515-6(12)(d)(iv)Rule requires the discharge piping to be equipped with (in order of placement from the wellhead) a smooth nosed sampling tap, a check valve, a pressure gauge, a means of measuring flow, and a shutoff valve. Notes:There is not a shut off valve. Deficiency Points: 5 Days until points become effective on IPS: 0 SDWIS Deficiency Description: S027 NO SHUT OFF VALVE ON WELL DISCHARGE PIPING Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS003 | WELL #3 79. Wellhead is sealed to prevent contamination. Rule: R309-515-6(6)(i)R309-515-6(6)(i) and R309-515-6(12)(b,c,d)require a sanitary seal be installed and maintained at the wellhead and discharge piping. This significant deficiency should be corrected within 120 days of notification or have a corrective action plan approved by Notes:Sounding tube not sealed Deficiency Points: 50 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S013 WELL LACKS THE REQUIRED WELL SEAL Sanitary Survey Category: SO SDWIS Severity Code: Significant Deficiency Wells | WS003 | WELL #3 81C. Pump to waste line downturned if it discharges to sewer/storm drain or allowing complete drainage if not downturned Rule: R309-515-6(12)(d)(ix)The discharge end of the pump-to-waste line shall be downturned. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:End of pump to waste line is upturned, with no provision for complete drainage. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: S011 WELL PUMP TO WASTE LINE NOT DOWNTURNED Sanitary Survey Category: PU SDWIS Severity Code: Significant Deficiency Pump Stations | PF001 | IOKA / LEDGE LANE PUMP FACILITY 172B. End of air relief piping covered with #14 mesh screen Rule: R309-550-6(6)(b), R309-540-6(2)The open end of the air relief vent pipe from automatic valves shall be provided with a #14 mesh, non-corrodible screen. This significant deficiency must be corrected within 120 days of notification or have a corrective action plan approved by DDW. Notes:The air/vac did not have a screen at the time of inspection but one was installed immediately after the inspection. Deficiency Points: 25 Days until points become effective on IPS: 120 SDWIS Deficiency Description: PS10 PUMP STATION OR HYDROPNEUMATIC TANK A/V VALVE RELIEF PIPING LACKS NO. 14 SCREEN