HomeMy WebLinkAboutDDW-2024-008541Water System:Date:6/27/2024
System Number:By:NDH
860 Outdoor Watering?Yes
87 Irrigation Zone:3
2451 ERC's that Irrigate:200
Total ERC's:3311 % ERC's that Irrigate:23%
Fire Protection?Yes Ave Irrigated Ac/ERC:0.1
Fire Flow(gpm):1000 Other acres Irrigated:0.0
Fire Duration(hr):2 Total Irrigated Acres:20
Source Capacity
Flow Indoor Outdoor Total
(gpm)(gpm)(gpm)(gpm)
WS004 CUWCD 1217
WS006 DCWCD 620
WS007 Upper Country 150
1987 1839 68 1907 104%yes
Storage Capacity
Volume Indoor Outdoor Fire Total
(gal)(gal)(gal)(gal)(gal)
ST001 Bridgeland 2,000,000
ST002 Ioka 750,000
ST003 Upalco 150,000
ST004 Vonsville 500,000
ST005 Pleasant Valley 100,000
3,500,000 1,324,400 50,560 120,000 1,494,960 234%yes
* Use ERC Calculations tab and include page in final printout
** Does not separate fire suppression storage from domestic storage
Sufficient?
(y/n)
Percent of
Required
Sufficient?
(y/n)
Actual
Desc.Name
Total:
Required
Actual Required**
Name Desc.
Percent of
Required
Total:
Public Water System Source and Storage Capacity Calculations
Residential Connections:
Other Connections:
*ERC's of Other Connections:
Johnson Water District
07006
Page 1 of 2
Number of
People per
Camp site
Demand
(GPD/person)
Calculated
GPD/site or pad
ERC/site or
pad
# of Sites
or pads ERCs
0 60 0 0.000 0 0.0
0 20 0 0.000 0 0.0
0 5 0 0.000 0 0.0
N/A N/A 100 0.125 0 0.0
Total:0
Roadway Rest Stop w/ flushometer valves
Demand
(GPD/vehicle)
ERC/1000
vehicles
served
# of Vehicles
served per day ERCs
7 8.8 0 0
Commercial or Industrial Connections
Number of
Residential
Connections
water used by
residential
connections
(gal/yr)
Water used by
commer/indus
connections
(gal/yr)*
ERC's of
Comm/indus
Connections
860 128,703,999 366,710,000 2,451
Total ERC's of non-residential connections 2,451
* Does not include 328.9 MG of passthrough flow
Campgrounds
Modern Recreation Camp
ERC Calculations for non-residential connections
Semi-Developed Camp w/o flush toilets
Semi-Developed Camp w/ flush toilets
RV Park
Facility Type