August 29, 2023
Brian Turner
Canyonlands NP – Needles District HQ
2282 SW Resources Blvd Canyonland National Park
Moab, UT 84532
Subject: New Treatment Plant Monitoring Requirements for Canyonlands NP – Needles
District HQ, UTAH19042
Dear Brian Turner:
The Division of Drinking Water (The Division) recently became aware of a treatment plant (labeled as
“Needles Water Building Chlorinator” (TP004) in the Division’s database) which is operated to reduce
Iron, Manganese and Turbidity levels at the Cave Springs Well (WS004) prior to entry into the distribution
system.
In accordance with R309-215-6(2)(a), additional monitoring requirements have been assigned to this
facility (TP004) for the contaminants for which the treatment process has been installed.
The new monitoring requirements for this treatment plant are given below. These requirements will remain
in place for six months. If after six months the results demonstrate effective removal of the contaminants of
concern, monitoring requirements may be reduced from monthly to quarterly sampling. The next samples
will be due sometime between 09/01/2023-09/30/2023.
Facility with new
requirements Analyte(s)
Required # of
samples Sampling
Frequency Next Due Date Rule
Reference
TP004 Needles Water Building
Chlorinator Iron 1 Monthly 09/01/2023-
09/30/2023
R309-215-
6(2)(a)
Manganese 1 Monthly 09/01/2023-
09/30/2023
R309-215-
6(2)(a)
Turbidity 1 Monthly 09/01/2023-
09/30/2023
R309-215-
6(2)(a)
Nitrate 1 Yearly 01/01/2023-
12/31/2025
R309-205-
5(4)(a)
Sulfate 1 Every Three Years 01/01/2023-
12/31/2025
R309-205-
5(3)(a)
Brian Turner
Page 2 of 2
August 29, 2023
An updated monitoring schedule is enclosed and is also available to view any time at waterlink.utah.gov
under the Water Monitoring section.
Recommendations
It is the Division’s understanding that Canyonlands NP – Needles District HQ has occasionally
experienced discolored water throughout the system. Based on this the Division has the following
recommendations:
1) When monitoring the treated water for iron, manganese, and turbidity, also monitor the Cave
Springs Well (WS004) before treatment for iron, manganese, and turbidity. This additional
monitoring will provide information on the effectiveness of the treatment process and could assist
in optimizing the treatment.
2) When a discolored water complaint is received, take the following samples:
a. Iron, manganese, turbidity, chlorine residual, and Langlier index at the site experiencing
discolored water.
b. Iron, manganese and turbidity of the treated water.
Flushing is also recommended to clear up the colored water.
There are handheld analyzers available from companies like Hach that would allow for analysis of iron and
manganese on site, as well as turbidity. These kits would allow for quicker response to these issues and for
more frequent confirmation of the treatment process performance.
Thank you for your efforts in maintaining a safe drinking water system. If you have questions concerning
your sampling requirements, please contact David Kruse at 385-566-7789 (dbkruse@utah.gov).
Sincerely,
Mark Berger
Monitoring and Standards - Implementation Manager
Enclosure – Monitoring Schedule
cc: Brain Turner, Canyonlands NP – Needles District HQ, brian_turner@nps.gov
Mark Berger, Division of Drinking Water, mberger@utah.gov
Sarah Page, Division of Drinking Water, sepage@utah.gov
Ryan Dearing, Division of Drinking Water, rdearing@utah.gov
Russell Seeley, Department of Environmental Quality, rseeley@utah.gov
Ronnie Nieves, San Juan County Health Department, rnieves@sanjuancounty.org
David Kruse, Division of Drinking Water, dbkruse@utah.gov
Utah Department Of Environmental Quality
Division Of Drinking Water
Admin Contacts
Water Monitoring Report
BACTERIOLOGICAL MONITORING
MONITORING REQUIREMENTS BY FACILITY
CANYONLANDS NP -
NEEDLES DISTRICT HQ
PWS ID: UTAH19042 Rating: Approved 04/09/1996 Active
Legal Contact
NPS - CANYONLANDS NP
BRIAN EUGENE TURNER
2282 SW RESOURCES BLVD
CANYONLAND NATIONAL PARK
MOAB, UT 84532
Phone: 435-259-4712
County: SAN JUAN COUNTY
System Type: Transient Non-Community
Population: 406
Site Updates
Last Inventory Update: 07/13/2023
Last Surveyor Update: 09/14/2020
Surveyor: RICK MEYER
Operating Period: 1/1 - 12/31
Last IPS Update: 08/24/2023 14:10:00
Consumptive Use Zone
Irrigation Zone: 4
Date: 02/15/2013
Name Title Office Emergency Email
TURNER, BRIAN EUGENE 435-259-8859
ext 20
435-260-2329 brian_turner@nps.gov
Sample Count Type Frequency Schedule Begin Schedule End Analyte Name
1 Routine Monthly 04/01/2016 COLIFORM (TCR)
ID NAME
TP004 NEEDLES WATER BUILDING CHLORINATOR
Name Sample
Count Type Frequency Last Sampled Next Sample Due
IRON 1 Routine Monthly 09/01/2023 - 09/30/2023
MANGANESE 1 Routine Monthly 09/01/2023 - 09/30/2023
NITRATE 1 Routine Yearly 01/01/2023 - 12/31/2023
SULFATE 1 Routine 3 Years 01/01/2023 - 12/31/2025
TURBIDITY 1 Routine Monthly 09/01/2023 - 09/30/2023
DEQ | Drinking Water
Run Date: 08/24/2023 18:44:43 | Rating: Approved UTAH19042 CANYONLANDS NP - NEEDLES DISTRICT HQ page 1 of 1