HomeMy WebLinkAboutDDW-2024-005959
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144830 • Salt Lake City, UT 84114-4830
Telephone (801) 536-4200 • Fax (801) 536-4211 • T.D.D. (801) 536-4284
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
SPENCER J. COX
Governor
DIEDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Tim Davis
Director
August 8, 2023
Kraig Christensen
Bountiful City Water System
260 W 1050 S
Bountiful, UT 84010
Subject: Public Notice Requirement and Increased Monitoring for Use of Zesiger Well
(WS001), Bountiful City Water System: UTAH06015
Dear Kraig Christensen:
This letter is an official notification that according to the Division of Drinking Water’s (the
Division) records, the Zesiger Well (identified as WS001 in the Division’s database) is in
violation of the Gross Alpha Particle Activity standard as given in R309-200-4. The Gross Alpha
Particle Activity maximum contaminant level (MCL) is 15 pCi/L and compliance with the MCL is
based on a running annual average (RAA). The RAA for the Zesiger Well (WS001) is 18.8 pCi/L.
The MCL exceedance was determined after the April 11, 2023 sample where Gross Alpha Particle
Activity was found to be 27.8 pCi/L.
Given that the Zesiger Well (WS001) is used only as an emergency source and is ran to waste
during sampling events, a violation has not been issued. However, considering that the Zesiger
Well (WS001) does not comply with the drinking water standards given in R309-200-4, this
source shall not feed into the distribution system unless a water advisory public notice is issued to
connections served for the duration of time that the source supplies drinking water.
Should Bountiful City Water System (the system) decide to temporarily put the Zesiger Well
(WS001) into the distribution system during an emergency situation, the system shall notify the
Division in writing prior to placing the Zesiger Well online. An up-to-date public notice document
including the four most recent quarters of radionuclide data and the standard health language
presented in R309-220-15 shall be included in the correspondence.
As described in R309-220-6(3), the public notice shall be delivered to connections through both of
the following avenues:
1. Mail or direct delivery to each customer receiving a bill and to other service connections to
which water is delivered by the public water system.
Kraig Christensen
Page 2 of 2
August 8, 2023
2. Any other method reasonably calculated to reach other persons regularly served by the
system. Other methods may include postings on the city website, social media pages, news
publications and physical postings of the notice in conspicuous locations throughout the
area which is served by the Zesiger Well (WS001)
A copy of the public notice must be submitted to the Division at ddwreports@utah.gov and
dbkruse@utah.gov prior to delivery to the public.
Additionally, in accordance with R309-205-7(1)(e), the system must now take quarterly samples
for Gross Particle Activity, Radium-226, Radium-228 and Combined Uranium. The requested
samples have been added to the systems water monitoring report found on Waterlink.utah.gov.
These samples are due sometime between 07/01/2023-09/30/2023.
Thank you for your efforts in maintaining a safe drinking water system. If you have questions or
need further assistance, please contact David Kruse, at dbkruse@utah.gov or (385) 566-7789.
Sincerely,
Mark Berger
Monitoring and Standards Section Manager
Enclosures: Tier 2 Radionuclide Public Notice Template
Water Monitoring Schedule
cc: Kraig Christensen, Bountiful City Water System, kchristensen@bountiful.gov
Jay Clark, Davis County Health Department, jsclark@co.davis.ut.us
Mark Berger, Division of Drinking Water, mberger@utah.gov
David Kruse, Division of Drinking Water, dbkruse@utah.gov
Utah Department Of Environmental Quality
Division Of Drinking Water
Admin Contacts
Water Monitoring Report
BACTERIOLOGICAL MONITORING
Disinfection ByProduct Stage 2 Monitoring
Other Distribution Monitoring
MONITORING REQUIREMENTS BY FACILITY
BOUNTIFUL CITY WATER
SYSTEM
PWS ID: UTAH06015 Rating: Approved 06/12/2017 Active
Legal Contact
BOUNTIFUL CITY CORP
KRAIG WILLIAM CHRISTENSEN
260 W 1050 S
BOUNTIFUL, UT 84010
Phone: 801-298-6180
County: DAVIS COUNTY
System Type: Community
Population: 37,500
Site Updates
Last Inventory Update: 04/04/2023
Last Surveyor Update: 08/17/2021
Surveyor: NAGENDRA DEV
Operating Period: 1/1 - 12/31
Last IPS Update: 08/02/2023 14:10:00
Consumptive Use Zone
Irrigation Zone: 4
Date: 02/15/2013
Name Title Office Emergency Email
CHRISTENSEN, KRAIG WILLIAM 801-298-6180 kchristensen@bountiful.gov
Sample Count Type Frequency Schedule Begin Schedule End Analyte Name
40 Routine Monthly 01/01/1991 COLIFORM (TCR)
Sample Count Type Frequency Sample Label
4 Routine Quarterly UTAH06015 DS001 Sample ID
below
ID Site Last Sample Next Sample Due
MR001 1964 RIDGEHILL DR 07/11/2023 10/01/2023-12/31/2023
MD201 1447 N 400 W 07/11/2023 10/01/2023-12/31/2023
MD202 824 S 450 W 07/11/2023 10/01/2023-12/31/2023
MD203 421 CHELSEA DR 07/11/2023 10/01/2023-12/31/2023
Sample during the following months: July, October, January, April
Analyte Name ID Sample
Count Type Frequency Last Sampled Next Sample Due
LEAD AND COPPER DS001 30 Routine 3 Years 2022 06/01/2025-09/30/2025
ASBESTOS DS001 1 Routine 9 Years 06/08/2021 01/01/2029 - 12/31/2037
DEQ | Drinking Water
Run Date: 08/02/2023 21:42:46 | Rating: Approved UTAH06015 BOUNTIFUL CITY WATER SYSTEM page 1 of 3
ID NAME
SS234 MUELLER ENTRY POINT - 12, 13, TP014
Name Sample
Count Type Frequency Last Sampled Next Sample Due
INORGANICS-COMPL 1 Routine 9 Years 05/03/2022 01/01/2029 - 12/31/2037
NITRATE 1 Routine Yearly 05/03/2022 01/01/2023 - 12/31/2023
RADS - COMPLIANCE 1 Routine 9 Years 01/01/2020 - 12/31/2028
SULFATE,SODIUM,TDS 1 Routine 9 Years 05/03/2022 01/01/2029 - 12/31/2037
VOC-COMPL 1 Routine 6 Years 02/18/2020 01/01/2026 - 12/31/2031
SS986 SAMPLING STATION - 03 09
Name Sample
Count Type Frequency Last Sampled Next Sample Due
INORGANICS-COMPL 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
NITRATE 1 Routine Yearly 05/03/2022 01/01/2023 - 12/31/2023
PESTICIDES-COMPL 2 Routine 3 Years 02/07/2023 07/01/2023-09/30/2023
RADS - COMPLIANCE 1 Routine 3 Years 03/10/2021 01/01/2023 - 12/31/2025
SULFATE,SODIUM,TDS 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
VOC-COMPL 1 Routine 3 Years 05/12/2022 01/01/2023 - 12/31/2025
TP016 RADIUM BLEND PT FOR WS015
Name Sample
Count Type Frequency Last Sampled Next Sample Due
COMBINED RADIUM (-226 & -228)1 Routine Monthly 05/10/2023 08/01/2023-08/31/2023
GROSS ALPHA, EXCL. RADON & U 1 Routine 3 Years 04/26/2022 01/01/2023 - 12/31/2025
INORGANICS-COMPL 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
NITRATE 1 Routine Yearly 05/10/2023 01/01/2024 - 12/31/2024
PESTICIDES-COMPL 2 Routine 3 Years 02/07/2023 07/01/2023-09/30/2023
SULFATE,SODIUM,TDS 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
VOC-COMPL 1 Routine 3 Years 05/12/2022 01/01/2023 - 12/31/2025
WS001 ZESIGER WELL
Name Sample
Count Type Frequency Last Sampled Next Sample Due
COMBINED URANIUM 1 Routine Quarterly 07/01/2023 - 09/30/2023
GROSS ALPHA, EXCL. RADON & U 1 Routine Quarterly 04/11/2023 07/01/2023 - 09/30/2023
INORGANICS-COMPL 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
NITRATE 1 Routine Yearly 05/10/2023 01/01/2024 - 12/31/2024
PESTICIDES-COMPL 2 Routine 3 Years 02/07/2023 07/01/2023-09/30/2023
RADIUM-226 1 Routine Quarterly 04/11/2023 07/01/2023 - 09/30/2023
RADIUM-228 1 Routine Quarterly 04/11/2023 07/01/2023 - 09/30/2023
SULFATE,SODIUM,TDS 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
VOC-COMPL 1 Routine 3 Years 05/12/2022 01/01/2023 - 12/31/2025
WS007 CITY SHOP WELL
Name Sample
Count Type Frequency Last Sampled Next Sample Due
INORGANICS-COMPL 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
NITRATE 1 Routine Yearly 05/10/2023 01/01/2024 - 12/31/2024
PESTICIDES-COMPL 2 Routine 3 Years 02/07/2023 07/01/2023-09/30/2023
RADS - COMPLIANCE 1 Routine 3 Years 06/08/2022 01/01/2023 - 12/31/2025
SULFATE,SODIUM,TDS 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
VOC-COMPL 1 Routine 3 Years 06/08/2022 01/01/2023 - 12/31/2025
WS010 VIEWMONT WELL
DEQ | Drinking Water
Run Date: 08/02/2023 21:42:46 | Rating: Approved UTAH06015 BOUNTIFUL CITY WATER SYSTEM page 2 of 3
Name Sample
Count Type Frequency Last Sampled Next Sample Due
INORGANICS-COMPL 1 Routine 3 Years 11/08/2022 01/01/2023 - 12/31/2025
NITRATE 1 Routine Yearly 05/10/2023 01/01/2024 - 12/31/2024
PESTICIDES-COMPL 2 Routine 3 Years 02/07/2023 07/01/2023-09/30/2023
RADS - COMPLIANCE 1 Routine 3 Years 11/08/2022 01/01/2023 - 12/31/2025
SULFATE,SODIUM,TDS 1 Routine 3 Years 11/08/2022 01/01/2023 - 12/31/2025
VOC-COMPL 1 Routine 3 Years 11/08/2022 01/01/2023 - 12/31/2025
WS015 SUBCONSERV WELL
Name Sample
Count Type Frequency Last Sampled Next Sample Due
COMBINED RADIUM (-226 & -228)1 Routine Monthly 05/10/2023 08/01/2023-08/31/2023
WS018 100 E WELL (REPLACE)
Name Sample
Count Type Frequency Last Sampled Next Sample Due
INORGANICS-COMPL 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
NITRATE 1 Routine Yearly 05/10/2023 01/01/2024 - 12/31/2024
PESTICIDES-COMPL 2 Routine 3 Years 02/07/2023 07/01/2023-09/30/2023
RADS - COMPLIANCE 1 Routine 3 Years 03/10/2021 01/01/2023 - 12/31/2025
SULFATE,SODIUM,TDS 1 Routine 3 Years 05/03/2022 01/01/2023 - 12/31/2025
VOC-COMPL 1 Routine 3 Years 05/12/2022 01/01/2023 - 12/31/2025
Grouped Source Sampling Stations
Sample Group ID Sample Group
8081 13
Source ID Source Name Sample Group Details System
WS013B LOWER MUELLER WELL TO MILL
CREEK WTP
UTAH06015 BOUNTIFUL CITY
WATER SYSTEM
20021 SS234 - Mueller Entry Point
Source ID Source Name Sample Group Details System
WS013 LOWER MUELLER WELL UTAH06015 BOUNTIFUL CITY
WATER SYSTEM
TP014 MUELLER PARK WTP UTAH06015 BOUNTIFUL CITY
WATER SYSTEM
WS012 UPPER MUELLER WELL UTAH06015 BOUNTIFUL CITY
WATER SYSTEM
7986 UTAH SAMPLING STATION SS986
Source ID Source Name Sample Group Details System
WS003 CALDER WELL 1 UTAH06015 BOUNTIFUL CITY
WATER SYSTEM
WS009 CALDER WELL 2 UTAH06015 BOUNTIFUL CITY
WATER SYSTEM
DEQ | Drinking Water
Run Date: 08/02/2023 21:42:46 | Rating: Approved UTAH06015 BOUNTIFUL CITY WATER SYSTEM page 3 of 3