HomeMy WebLinkAboutDDW-2024-008417Sanitary Survey - Deficiency Report
PWS Number:UTAH22018 Deficiency Points:25 Survey Date:06/17/2024
Survey Name:WOODLAND MUTUAL
WATER CO
Surveyor:Tom McOmie
Sanitary Survey Category: SO
SDWIS Severity Code: Significant Deficiency
Management and Operations | DS001 | UTAH22018 DISTRIBUTION SYSTEM
22. For a community water system with water sources that require power to produce sufficient flow, system is equipped with standby power
option.
Rule: R309-515-6(2)(a)Rule requires a community water system without naturally flowing water sources, such
as springs or flowing wells, to have one or more of the system's sources equipped for
operation during power outages. To ensure continuous service when the primary power
has been interrupted, a redundant power supply is required. A redundant power
supply may include a transfer switch for auxiliary power such as a generator or a
power supply service with coverage from two independent substations. This significant
deficiency must be corrected within 120 days of notification or have a corrective action
plan approved by DDW.
Notes:They have a contractor doing the job but they are waiting on the part. It could take up to 3
months to get the part.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: S033 COM SYSTEM WITHOUT NATURALLY FLOWING SOURCES LACKS BACKUP
POWER FOR AT LEAST ONE WATER SOURCE