HomeMy WebLinkAboutDAQ-2024-005008
1
DAQC-149-24
Site ID 16015 (B5)
MEMORANDUM
TO: FILE – HOLLY ENERGY PARTNERS – Light Oil Dock
THROUGH: Harold Burge, Major Source Compliance Section Manager
FROM: Rob Leishman, Environmental Scientist
DATE: February 16, 2024
SUBJECT: Holly Energy Partners, Light Oil Dock (Holly LOD), Major, MACT, SIP, Title V,
Davis County, FRS # UT00000049001100013
INSPECTION TYPE: State Electronic Data Report (SEDR) Review
REVIEW DATE: February 16, 2024
SOURCE LOCATION: West Bountiful/Davis County
SOURCE CONTACT: Daria Underwood – 214-954-3935
APPLICABLE
REGULATIONS: Title V operating permit – 1100458001 – dated February 8, 2021
SOURCE INSPECTION
EVALUATION: With the exception of sources that only monitor for opacity, quarterly
report memoranda will only address the findings of the quarterly report.
Approval Order and Title V permit conditions addressing continuous
emission monitoring requirements will be addressed in Holly LOD’s
relative accuracy performance specification test review memorandum.
SOURCE REVIEW EVALUATION:
Fourth Quarter 2023
% Monitor Availability (MA) Performance Test Dates
(N/A to Opacity)
Summary of Excess Emissions During Point
Source Operation
Point
Source
Op.
hrs. Channel MA CGA Lin RATA Point
Source Channel Hrs. Limitation
LOD 2208 VOC 99% 12/05/23 11/21/23 LOD VOC 0.00 10000 ppm - 6 hour
RA
1 8 2
2
Excess Emission Report - Hourly Summary
Point
Source Channel
Startup
&
Shutdown
Control
Equipment
Problems
Process
Problems
Other
Known
Causes
Unknown
Causes
Emission
Limit
LOD VOC 0 0 0 0 0 10000 ppm – 6-hour RA
CMS Performance Summary - Hourly Summary
Point
Source Channel Monitor
Malfunction
Non-monitor
Malfunction
QA
Calibrations
Other
Known
Causes
Unknown
Causes
LOD VOC 0 0 11 0 0
Pollutant Concentration
Exceeded Span of CEM
Monitor Outage During
Point Source Operation
Alternate
Sampling CEM Modifications
0 Hours 0 Hours 0 Hours 0 Events
SOURCE INSPECTION
SUMMARY EVALUATION: Holly LOD maintains its CEMS as required in R307-170 and 40 CFR
60.13.
CURRENT
RECOMMENDATIONS: All deviations appear to be a result of breakdown or process related
problems that do not warrant issuing a violation. Holly LOD was in
compliance during this reporting period. No further enforcement action
is necessary.
Holly LOD’s NSPS monitoring system meets the performance standards
of 40 CFR 60, Appendix B Performance Specifications.
HIGH PRIORITY
VIOLATOR (HPV): No
RECOMMENDATION
FOR NEXT INSPECTION: Check DAS for daily zero and span drift.
Check the QC program to ensure that monitor drift is being tracked and
that the source can identify excessive drift.
ATTACHMENTS: Excel spreadsheet review
Corporate Office: 2828 N. Harwood, Suite 1300 Dallas, TX 75201-1507 214-871-3555
Operations Office: 1602 West Main Street Artesia, NM 88210 575-748-4000
January 26, 2024
Utah Division of Air Quality
195 North 1950 West
Salt Lake City Utah 84116
Re: 4th Quarter 2023 CEMS Report
Woods Cross Terminal, Approval Order DAQE-AN010120023B-07
Holly Energy Partners
Dear Sir/Madam:
Enclosed please find the Q4-2023 Woods Cross Terminal Continuous Emission Monitoring System (CEMS) Report.
Per Utah Administrative Code R307-170-9, the electronic ASCII report file was sent to Rob Leishman, UDAQ, on
January 26, 2024, via e-mail. The following information is applicable to report contents:
1. The continuous monitoring system calibration and drift checks were routinely performed, and a quarterly
cylinder gas audit (CGA) was completed on 12/5/2023 and found within the required performance
specifications.
2. The data used to show compliance with the standard were obtained in accordance with approved methods
and procedures.
3. The minimum data requirements have been met with 0% CEMs missing data. CEMs downtime was 0.52%
related to required QC (daily span/zero checks) and CGA during the 4th quarter.
4. Compliance with the general requirements under Utah Administrative Code R307-170-5 has been achieved
during the reporting period.
I certify under penalties of law that, based upon inquiry of personnel involved, and to the best of my knowledge,
the statements and information contained in this report are truthful and accurate, and are a complete record of all
monitoring-related events that occurred during the reporting period.
If you have any questions or need additional information, please contact me at (214) 954-6690.
Sincerely,
Jason Leik
Environmental Manager
Attachment: (1/1) HEP CEMS EER Worksheet, 4th Quarter 2023
Attachment: HEP CEMS EER Worksheet, 4th Quarter 2023
(Note: A copy of the attached EER worksheet, in CSV format, was submitted to Mr. Rob Leishman on
January 26, 2024, via email from Tawnya Chott, ERM, on behalf of HEP)
100 Mark T CunninghamHolly Ener P.O. Box 1260 Artesia, New M 011-00013(214) 954-6690 Jason Leik
110 LOD 4 2023 2208
200 LOD VOC IR 8400D 5086 5000 20,000 8/8/2016 VRU
220 LOD VOC
230 LOD VOC 0 0 0 0
250 LOD VOC 11/21/2023 12/14/2022 12 ppm 642 714 1.43%pass
260 LOD VOC 12/5/2023 1 FF6611 8/12/2024 Certified Master percent 0.513 0.508 1.05%pass low
260 LOD VOC 12/5/2023 2 FF37299 8/12/2024 Certified Master percent 1.087 1.123 -3.24%pass mid
300 LOD VOC 0.52%11.43 0 0 11.43 0 0
310 LOD VOC 0 0.00%0 0 0 0 0 10000 ppm 6 hour RA
460 LOD VOC NA NA 0
700 701 Startup/Shutdown
700 702 Control Equipment Problems
700 703 Process Problems
700 704 Other Known Causes
700 705 Unknown Causes
720 721 Monitor Equipment Malfunction
720 722 Nonmonitor Equipment Malfunction
720 723 QA Calibrations
720 724 Other Known Causes
720 725 Unknown Causes
730 703 A Power failure.
730 703 B Control valve failure.
730 703 C Pump failure
730 704 A Other known causes. Refinery product process change for winter grades
730 705 A Unknown cause.
730 721 A Daily calibration check exceedance. Cause of drift unknown. Recalibrated instrument.
730 721 B Data recorder failure.
730 721 C Power failure. No loading during outage.
730 721 D Monitor failure
730 722 A VRU Equipment failure. VCU used for control.
730 723 A (QA/QC) - VCU used for control.
730 724 A Meter proving. VCU used for control.
730 724 B VRU maintenance. VCU used for control.
730 724 C Monitor maintenance.
Holly LOD EER 4Q2023
Point Source Information Late Expired Cal. Gas Valid Cal. Gas Days Yes No
1 Type Code 100
(Company Information)Type Code Company Manager Company Name AIRS # Phone Number
Environmental
Contact
1 100
Mark T
Cunningham 01100013 (214) 954-6690 Jason Leik0
1 100 0 0 0 0
1 Type Code 110
(Point Source Identification)Type Code Point Source
Quarter
1 - 4 Year
Point Source
Operating Hrs. in
Quarter
1 110 4 2023 2208
1 110 0 0 0
1 Type Code 200
(Monitor Identification)Type Code Point Source Channel Manufacturer Model No. Monitor SN Low Span High Span Installation Date
Monitor
Location
1 200 VOC IR 8400D 5086 5000 20000 8/8/2016 VRU
1 200 0 0 0 0 0 0 1/0/1900 0
1
Type Code310
(Excess Emissions)
SUMMARY REPORT
Type Code Channel
Total Hours of Excess
Emissions
Excess Emissions -
% of Total
Operating Hours
RC 701 Hours -
start
up/Shutdown
RC 702 Hours-
Control Equipment
Problems
RC 703 Hours -
Process Problems
RC 704, 706, 707
Hours -Other Known
Causes
RC 705 Hours -
Unknown
Causes
Emission
Limitation
Emission
Limitation
Units
Emission
Limitation
Averaging
Period
1 TRUE 310 VOC 0 0.00% 0 0 0 0 0 10000 ppm 6 hour RA
1 310 0 0 0 0 0 0 0 0 0
1 Type Code 300 (CMS
Performance Summary) Type Code Channel
Point Source Operating
Hours
Downtime - % of
Total Operating
Hours
Total CMS
Downtime
RC 721 Hours -
Monitor
Malfunction
RC 722 Hours -
Non-monitor
Malfunction
RC 723 Hours -
QA Calibrations
RC 724 Hours -
Other Known
Causes
RC 725
Hours -
Unknown
Causes
1 TRUE 300 VOC 2208 0.52% 11.43 0 0 11.43 0 0
1 300 0 0 0 0 0 0
1
Type Code 250
(Performance Specification
RATA Results)
Type Code Channel
Date of Most Current
RATA
Date of Preceding
RATA
Months Between
RATA's
Units of
Measurement CEM Value Reference Method
Value
Relative
accuracy Pass/ Fail
1 342 Days 250 VOC 11/21/23 12/14/22 12 ppm 642 714 1.43% pass
1 0 Days 250 0 01/00/00 01/00/00 0 0 0 0 0.00% 0
1 Type Code 260
(CGA Results)Type Code Channel Date Audit Point No. Cylinder ID
Cylinder
Expiration Date
Type of
Certification
Units of
Measurement CEM Value Cylinder
Value
Precision
%Pass/ Fail Range - High or
Low
1 Valid Cal. Gas 260 VOC 12/05/23 1 FF6611 08/12/24 Certified Master Gas percent 5130 5080 1.05% pass low
1 Valid Cal. Gas 260 VOC 12/05/23 2 FF37299 08/12/24 Certified Master Gas percent 10870 11230 -3.24% pass mid
1 260 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0
1 Type Code 270
(Linearity Test Results)Type Code Channel Date Audit Point No. Cylinder ID
Cylinder
Expiration Date
Type of
Certification
Units of
Measurement CEM Value Cylinder
Value
Precision
%Pass/ Fail Range - High or
Low
1 270 0 01/00/00 0 0 01/00/00 0 0 0 0 0.00% 0 0
1
Type Code 210
(Pollutant Concentration
Exceeded Span of CEM)
Type Code Channel Start Date Start Time End Date End Time Hours
1 0 0 0 1/0/00 0:00 1/0/00 0:00
1
1 None Reported
1 0 TC 220 Hours 0.00 TC 220 Hours 0.00 TC 230 Hours 0.00 Events 0.00 Hours 0.00 Events 0.00 0.00
1 11.43 TC 300 Hours 11.43 FALSE
Yes None Reported None Reported None Reported None Reported None Reported
Point Source
Point Source
Point Source
Point Source
Point Source
Point Source
Yes
LOD
0
LOD
LOD
LOD
0
Type Code 550
(Changes in Operation in
Control Equipment When
CEM Data Not Available)
Type Code 500
(Boiler Operating Days
w/o 18 Hours of Data)
Holly Energy Partners Operating, L.P.
0
Type Code 450
(Data Excluded)
LOD
0
LOD
0
Type Code 210
(Pollutant Concentration
Exceeded Span of CEM)
Type Code 220
(Monitor Outage
During Point Source Operation)
Type Code 230
(Manual Sample - Alternate
Sampling During Monitor
Outage)
Type Code 240
(CEM Modifications)
Type Code 530
(Excess Emissions During
Emergency Conditions)
0
LOD
0
0
0
Holly LOD EER 4Q2023
Relative Accuracy Overview
Point Source Channel
Date of Most
Current
RATA
Date of
Preceding
RATA
Months Between
RATA's
Units
Measured CEM Value Reference Method
Value
Relative
Accuracy Pass/ Fail
LOD VOC 11/21/23 12/14/22 12 ppm 642 714.00 1.43% pass
*
NSPS CGA Fourth 2023
Audit Gas Ranges Audit Gas Ranges
AP1 Low AP2 Low AP1 High AP2 High
LOD VOC 12/5/23 20000 5080 4000 to 6000
LOD VOC 12/5/23 20000 11230 10000 to 12000
Point Source Channel Audit Date Low Span Audit Gas Used High Span Audit Gas Used
Holly LOD EER 4Q2023
Monitoring Information TC 210, 230, & 240
Type Code 210
(Pollutant Concentration Exceeded Span of CEM) - 500 (All)
*
Sum of Hours Column Labels
Row Labels (blank) Grand Total
(blank)0 0
Grand Total 0 0
*
Type Code 230
(Manual Sample - Alternate Sampling During Monitor Outage) - 500 (All)
*
Sum of Hours Column Labels
Row Labels (blank) VOC Grand Total
(blank)0 0
LOD 0 0
Grand Total 0 0 0
*
Type Code 240
(CEM Modifications) - 100 (All)
*
Count of Channel Column Labels
Row Labels (blank) Grand Total
(blank)
(blank)
Grand Total
Holly LOD EER 4Q2023
Type Code 220
(Monitor Outage During Point Source Operation) - 600 (All)
*
Sum of Hours Column Labels
Row Labels (blank) Grand Total
(blank)
(blank)
0 0
LOD
VOC
0 0 0
Grand Total 0 0
Holly LOD EER 4Q2023
VOC/THC *
VOC/THC Type Code 460 (VOC/THC) - 6000 (All)
VOC/THC *
VOC/THC Count of Magnitude of Emissions Column Labels
VOC/THC Row Labels 0 Grand Total
VOC/THC LOD
VOC/THC #N/A 1 1
VOC/THC Grand Total 1 1
Holly LOD EER 4Q2023
Type Code 500
Before February 28, 2005 (Boiler Operating Days w/o 18 Hours of
Data) After February 28, 2005 (90% Operating Hours For each 30 BOD)
- 500
(All)
*
Count of Channel Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 510
(F-factor, Equations & Conversion Factors) - 500 (All)
Count of F-factor Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 520
(Minimum Data Not
Obtained <22/30 BODs) - 500
(All)
Count of Channel Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 530
(Excess Emissions During Emergency Conditions) - 500 (All)
Count of Date Column Labels
Row Labels Grand Total
Grand Total
*
Type Code 540
(Fuel Pre-treatment Credit SO2) - 500 (All)
Count of Date Column Labels
Row Labels Grand Total
Grand Total
*
TypeCode 550
(Changes in Operation in Control Equipment When CEM Data Not
Available) - 500
(All)
Column Labels
Row Labels Grand Total
Grand Total