HomeMy WebLinkAboutDDW-2024-008323154 EAST 14075 SOUTH • DRAPER, UTAH 84020 TEL: (801) 495-2224 • FAX: (801) 495-2225 June 4, 2024 Mr. Hunter Payne Utah Division of Drinking Water 195 North 1950 West Salt Lake City, Utah 84116 (385)278-9837 Subject: Exception Request South Weber Well #2 Reconstruction Plan Review File No.: 13638 Dear Mr. Payne: A recent review of the above referenced project noted that hypochlorite dosing pumps are sized to yield a concentration of 0.7 mg/L chlorine in the discharge stream of this well. On behalf of the Weber Basin Water Conservancy District (the District), we request an exception to rule R309-520-7(1)(c)(i) which states “the capacity of the chlorine feed equipment shall be sized to provide at least 2 mg/L during peak demand”. Given the target chlorine residual of 0.5 mg/L, the project team cannot foresee a scenario in which water operators would elect to dose at the specified rate. The system does meet the other requirements of rule R309-520-7(1)(c): “the feed equipment shall operate accurately over the design feeding range”; and, “the feed equipment shall be designed to maintain a detectable residual at all times, at all points within the intended area in the distribution system”. The District operates several sampling and dosing locations throughout their distribution network. The dosing pumps will be programmed to operate proportional to the well’s discharge as measured by the magnetic flow meter. Sincerely, Bowen Collins & Associates, Inc. Michael McFadden, P.E. Project Engineer CC: Jesse Moreno, Weber Basin Water Conservancy District