HomeMy WebLinkAboutDDW-2024-008313Sanitary Survey - Deficiency Report
PWS Number:UTAH29046 Deficiency Points:25 Survey Date:05/30/2024
Survey Name:VALLEY VIEW STAKE CAMP Surveyor:Cameron Draney
Sanitary Survey Category: TR
SDWIS Severity Code: Significant Deficiency
Hypochlorination (any type) | TP003 | CAMP CHLORINATOR
202. Where concentrated hypochlorite solutions are handled in containers of 55 gallons or LESS: some method of emergency eyewash provided
(a full eyewash station and shower is not required)
Rule: R309-520-7(3)(a)(i)Where hypochlorite solutions are used at remote locations or in quantities of 55 gallons
or less on site, safety showers are not required and alternative emergency eyewash may
be provided. This significant deficiency must be corrected within 120 days of
notification or have a corrective action plan approved by DDW.
Notes:No eye wash provided.
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: TD66 HYPOCHLORITE FACILITY LACKS A MEANS OF EMERGENCY EYEWASH