Loading...
HomeMy WebLinkAboutDAQ-2024-0083081 DAQC-536-24 Site ID 10320 (B4) MEMORANDUM TO: STACK TEST FILE – KERN RIVER GAS TRANSMISSION COMPANY – Fillmore Compressor Station THROUGH: Rik Ombach, Minor Source Oil and Gas Compliance Section Manager FROM: Kyle Greenberg, Environmental Scientist DATE: June 3, 2024 SUBJECT: Source: Fillmore Compressor Station – Turbine: Unit T-2 Location: Millard County, Utah Contact: Denise Kohtala: 801-937-6347 Tester: Alliance Technical Group Site ID #: 10320 Permit/AO #: DAQE-AN103200020-24, dated March 11, 2024 Subject: Review of Pretest Protocol dated May 30, 2024 On May 30, 2024, Utah Division of Air Quality (DAQ) received a protocol for testing of Unit T-2 at Fillmore Compressor Station in Millard County, Utah. Testing will be performed on July 9, 2024, to determine compliance with the emission limits found in Condition of II.B.2 of Approval Order DAQE-AN103200020-24 and 40 CFR Part 60, Subpart GG. PROTOCOL CONDITIONS: 1. RM 1 used to determine sample velocity traverses: OK 2. RM 3A used to determine O2 and CO2 concentrations: OK 3. RM 7E used to determine NOx emissions: OK 4. RM 10 used to determine CO emissions: OK 5. RM 19 used to determine exhaust effluent flows and mass emission rates: OK 6. RM 20 used to determine testing parameters for emissions from gas turbines: OK DEVIATIONS: None. CONCLUSION: The protocol appears to be acceptable. RECOMMENDATION: The methods outlined in the pretest protocol should be considered appropriate in meeting the testing requirements and to determine compliance with the AO and Subpart GG. ATTACHMENTS: Pretest Protocol, Notice of Test Date Confirmation