Loading...
HomeMy WebLinkAboutDAQ-2024-008247ffenpk PERMIT DEVIATION REPORT TO: Executive Secretary Utah Air Quality Board RE: Deviation Report for Permit # 2100036004 UTAH DEPABTMENT OF ENVIRONMENTAL OUALITY tvf;1y 11 ?i,ll Di'ViSiON OF AIR QUALIT\' DATE:osl09l2024 ln accordance with Operating Permit provision 1.5.2.b, and Utah Administrative Code (UAC) R307-415-6a (3XcXii), the following deviation report is submitted. 1 Dates that the deviation occurred: os I os 12024 and os I 07 12024 2 Permit conditions for which deviation occurred: ll.B.3.a. Operating temperature shall be no less than 1,360 degrees F. [Authority granted under R307-401-8(fXa) [BACfl; condition originated in DAqE-ANo1L7670008t21 Describe the deviation that occurred: RTo temperature fell below 1,360 degrees F for approximately 19 mins. Was the deviation due to and "upset condition" as defined in Section ll of the permit. NO 5 Describe the probable cause of the deviation: The cool down damper failed to open causing the flame to go out. 6 Describe any corrective actions or prevention measures taken: Cool down damper failed. ln accordance with Operating Permit Provision l.K and UAC R307-415-5b and based on information and belief formed after responsible inquiry t certify that the statement and information in this document are true, accurate and complete. Genpak, LLC 279LW Hwy 56 Cedar City, UT 84720 435-865-7025 Plant Manager REVIEWED Initials JBR Date 6/4/2024 Comp Status Meets File # 11767 Blue 2 cont monitor mech failure NFA