HomeMy WebLinkAboutDDW-2024-007886
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144830 • Salt Lake City, UT 84114-4830
Telephone (801) 536-4200 • Fax (801) 536-4211 • T.D.D. (801) 903-3978
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Tim Davis
Director
November 6, 2023
Cathy Christensen
Ross Springs Water System
Ashley Valley National Forest
355 N. Vernal Ave
Vernal, UT 84078
Dear Cathy Christensen:
Subject: Corrective Action Plan Closure UTAH05010-2023-01
On September 26, 2022, Ross Springs Water and the Division of Drinking Water entered into a Corrective
Action Plan (CAP). As of November 6, 2023, Ross Springs Water has successfully completed the
requirements listed in the CAP. The CAP is now officially closed, and the water system’s rating will remain
at an approved status with 60 Improvement Priority System (IPS) points.
The Division of Drinking Water recognizes that addressing deficiencies and violations can be difficult and
often requires significant financial and personnel resources. We would like to thank Ross Springs Water for
the efforts put forth in resolving the items, for your continued commitment to maintaining reliable
infrastructure, and for ensuring the safety of the drinking water provided to your customers.
Please find enclosed current copies of the completed CAP requirements, monitoring schedule, and IPS report
to help Ross Springs Water maintain compliance and an approved status. If you have any questions, please
contact Brandi Smith at (385) 515-1650 or brandismith@utah.gov.
If there is ever anything we can do to support you in your role of protecting public health, please contact us.
Sincerely,
Helen Lau
Compliance and Operator Assistance Section Manager
Division of Drinking Water
Enclosure
' ) 0 — * 1 E v A ? A B @ @ w B D ˜
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Tim Davis
Director
Completed CAP Requirements
Deficiency/Violation Date of
Occurrence
Plan to return to
compliance
Date of
Completion
IPS Points
Resolved
V012-ST001- End of storage
tank overflow pipe lacks a
No. 4 Screen
09/2022 Replace screen on
overflow pipe on storage
tank to a No.4 screen
11/06/2023 25
TD66-TP001- Hypochlorite
facility lacks a means of
emergency eye wash
09/2022 Ensure that there is an
emergency eye wash
station in the treatment
plant area
10/19/2022 25