HomeMy WebLinkAboutDDW-2024-007885
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144830 • Salt Lake City, UT 84114-4830
Telephone (801) 536-4200 • Fax (801) 536-4211 • T.D.D. (801) 903-3978
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Tim Davis
Director
November 8, 2023
Neal Winterton
Pleasant Grove City Water
70 South 100 East
Pleasant Grove, UT 84062
Dear Neal Winterton:
Subject: Corrective Action Plan Closure UTAH25022-2023-01
On September 14, 2022, Pleasant Grove City Water and the Division of Drinking Water entered into a
Corrective Action Plan (CAP). As of November 8, 2023, Pleasant Grove City Water has successfully
completed the requirements listed in the CAP. The CAP is now officially closed, and the water system’s
rating will remain at an approved status with 60 Improvement Priority System (IPS) points.
The Division of Drinking Water recognizes that addressing deficiencies and violations can be difficult and
often requires significant financial and personnel resources. We would like to thank Pleasant Grove City
Water for the efforts put forth in resolving the items, for your continued commitment to maintaining reliable
infrastructure, and for ensuring the safety of the drinking water provided to your customers.
Please find enclosed current copies of the completed CAP requirements, monitoring schedule, and IPS report
to help Pleasant Grove City Water maintain compliance and an approved status. If you have any questions,
please contact Brandi Smith at (385) 515-1650 or brandismith@utah.gov.
If there is ever anything we can do to support you in your role of protecting public health, please contact us.
Sincerely,
Helen Lau
Compliance and Operator Assistance Section Manager
Division of Drinking Water
Enclosure
' ) 0 — * 1 G v A ? A B @ ? w ? H ˜
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Tim Davis
Director
Completed CAP Requirements
Deficiency/Violation Date of
Occurrence
Plan to return to
compliance
Date of
Completion
IPS Points
Resolved
SS07-WS002 Deep rooted
vegetation in Spring
Collection Area
9/2022 Ensure the deep-rooted
vegetation is removed
from the spring
collection area
04/10/2023 25
SS08-WS002 Roots in
Spring Collection Pipes
09/2022 Ensure roots are no
longer in spring
collection pipes
04/10/2023 25
S013-WS006 Well lacks the
required well seal
09/2022 Ensure the well has the
proper well seal
02/08/2023 50
V005-ST001 Storage facility
vent not downturned at least
2 inches below any opening
09/2022 Ensure storage facility
vent is downturned at
least 2 inches
04/17/2023 25
V007-ST001 Storage tank
vent lacks a No. 14 Screen
09/2022 Add a No.14 screen to
the storage tank vent
02/08/2023 25
V010-ST001 Storage tank lid
not shoebox style
09/2022 Make sure that the
storage tank lid is
shoebox style
02/08/2023 25
V009-ST001 Storage tank lid
lacks a functioning gasket
between the lid and frame
09/2022 Make sure there is a
proper gasket between
the lid and frame
02/08/2023 25
V029-ST001 Storage tank
access opening lacks a lock
09/2022 Place a lock on the
storage tank access
opening
04/17/2023 25
V017-ST001 Storage tank
subject to contamination due
to unsealed openings
09/2022 Repair opening in the
storage tank, so it is no
longer subject to
contamination
04/17/2023 100
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Tim Davis
Director
V009-ST002 Storage tank lid
lacks a functioning gasket
between the lid and frame
09/2022 Make sure there is a
proper gasket between
the lid and frame
02/08/2023 25
V012-ST003 End of storage
tank overflow pipe lacks a
No. 4 Screen
09/2022 Ensure that the storage
tank overflow pipe has a
No. 4 screen
02/08/2023 25
V009-ST004 Storage tank lid
lacks a functioning gasket
between the lid and frame
09/2022 Make sure there is a
proper gasket between
the lid and frame
02/08/2023 25
V009-ST005 Storage tank lid
lacks a functioning gasket
between the lid and frame
09/2022 Make sure there is a
proper gasket between
the lid and frame
09/14/2022 25
V009-ST006 Storage tank lid
lacks a functioning gasket
between the lid and frame
09/2022 Make sure there is a
proper gasket between
the lid and frame
02/08/2023 25
V012-ST007 End of storage
tank overflow pipe lacks a
No. 4 Screen
09/2022 Ensure that the storage
tank overflow pipe has a
No. 4 screen
02/08/2023 25
S007-WS008 Well Casing
Vent not downturned
9/2022 Downturn the well
casing vent
09/08/2023 25
S013-WS017 Well lacks the
required well seal
09/2022 Ensure the well has the
proper well seal
09/08/2023 50
V011-ST001 End of storage
tank overflow lacks a
clearance of 12 inches
09/2022 Ensure the overflow on
storage tank has a 12-
inch clearance
11/02/2023 25
V009-ST003 Storage tank lid
lacks a functioning gasket
between the lid and frame
09/2022 Make sure there is a
proper gasket between
the lid and frame
04/10/2023 25
V011-ST005 End of storage
tank overflow lacks a
clearance of 12 inches
09/2022 Ensure the overflow on
storage tank has a 12-
inch clearance
11/01/2023 25