HomeMy WebLinkAboutDAQ-2024-007336January 3, 2023
Minor Source Compliance Section
Utah Division of Air Quality
Attn: Chad Gilgen
P.O. Box 144820
Salt Lake City Utah 84114-4820
Dear Mr. Gilgen,
The New Source Performance Standards for Small Industrial-Commercial-institutional Steam
Generating Units (NSPS Boilers) 40 CFR 60 Subpart Dc reporting the quantity of fuel other than
natural gas combusted during the reporting period for St. George Hospital Utah DAQ Site ID 12960.
-Six month reporting period covered under this is from July 1, through December 31, 2023.
-The 4-duel fuel boiler had a total of 12 hours of operation on diesel fuel for the reporting
period.
-A copy of the most recent diesel fuel analysis report is included as reference.
In accordance with Utah Administrative Code R307-415-5d and based on information and belief
formed after reasonable inquiry, I certify that the statements and information in this document are
true, accurate, and complete.
Sincerely,
Jim Blankenau, P.G.
Environmental Engineer
Intermountain Health, Canyons
383 W. Vine Street (4th floor),
Murray, UT 84124
801-484-6114
James.Blankenau@imail.org
Attachments: St. George Fuel Analysis Report
Initials: CG Date: 4-11-24
Compliance Status: In compliance -
Subpart Dc Semi-Annual Notification
File # 12960 (B2)
Fuel Analysis Report
North America:+1-877-808-3750
Based on ASTM D975 Standard Specification for Diesel Fuel.
Decision rule based on simple acceptance.
Account Information
Account Number:ONLINE-2622-0000
Company Name:ST GEORGE REGIONAL
HOSPITAL
Contact:ALAN ROBERTS
Address:1380 E. MEDICAL CENTER DR.
ST.GEORGE, UT 84790 US
Phone Number:435-703-0245
Component Information
Component ID:FOT-1 423159 DF
Secondary ID:
Fuel Type:DIESEL FUEL
Manufacturer:
Model:
Application:UNKNOWN
Tank Capacity:
Sample Information
Tracking Number:23111M61733
Lab Number:S-978268
Lab Location:Salt Lake City
Data Analyst:JUK
Sampled:02-May-2023
Received:04-May-2023
Completed:15-May-2023
Filter Information
Filter Change:Unknown
Filter Type:Information Requested
Micron Rating:0
Miscellaneous Information
Comments TEST RESULTS are within NORMAL PARAMETERS for this product.
Test Results
Test Method Test Name Result Min Max
ASTM D7220 Sulfur (ppm)6.8
ASTM D2709 Water and Sediment (%)<0.01
mod. ASTM D6304 Water by Karl Fischer (%)0.001
mod. ASTM D6304 Water by Karl Fischer (ppm)
Manufacturer Adenosine Triphosphate
Content (pg ATP / mL)
Manufacturer Aerobic Bacteria (Counts)
Manufacturer Bacteria (Counts)0
Manufacturer Fungi (Counts)Negative
Manufacturer Mold (Counts)0
mod. ASTM D6468 Thermal Stablity (%)98.1
mod. ASTM D445 Viscosity 40°C (cSt)2.47
mod. ASTM D445 Viscosity 100 °C (cSt)
mod. ASTM D664 Acid Number (mg KOH / g)
ASTM D7689 Cloud Point (°C)-16
ASTM D7346 Pour Point (°C)-27
ASTM D6371 Cold Filter Plug Point (°C)
ASTM D3828 Closed Cup Flash Point (°C)70.5
ASTM D7345
"Predicted D86"
Distillation Initial Boiling Point
(°C)174.1
ASTM D7345
"Predicted D86"Distillation 10% Recovered (°C)200.8
ASTM D7345
"Predicted D86"Distillation 50% Recovered (°C)251.1
ASTM D7345
"Predicted D86"Distillation 90% Recovered (°C)316.1
ASTM D7345
"Predicted D86"
Distillation Final Boiling Point
(°C)345.5
ASTM D976 Cetane Index 45.2
ASTM D7777 API Gravity 36.0
ASTM D7777 Density (g / mL)
Internal Method Specific Gravity
ASTM D4868 BTU Per Gallon (BTU / gal)
ASTM D4868 BTU Per Pound (BTU / lb)
ASTM D6079 Lubricity (µm)
ASTM D130 Copper Corrosion
ASTM D482 Ash Content (mass %)
ASTM D189 Carbon Residue (%)
ASTM D7371 % Biodiesel - FAME (%)
Elemental Analysis
mod. ASTM D5185 Result Min Max
Iron (ppm)1
Chromium (ppm)0
Nickel (ppm)0
Aluminum (ppm)0
Copper (ppm)0
Lead (ppm)0
Tin (ppm)0
Cadmium (ppm)0
Silver (ppm)0
Vanadium (ppm)0
Silicon (ppm)1
Sodium (ppm)0
Potassium (ppm)0
Titanium (ppm)0
Molybdenum (ppm)0
Antimony (ppm)0
Manganese (ppm)0
Lithium (ppm)0
Boron (ppm)0
Magnesium (ppm)0
Calcium (ppm)0
Barium (ppm)0
Phosphorus (ppm)1
Zinc (ppm)1
Particle Count (particles / mL)
ISO 4406 & mod. ISO 11500 Result Min Max
ISO Cleanliness Code / / / / / /
> 4μm
> 6μm
> 10μm
> 14μm
> 21μm
> 38μm
> 70μm
> 100μm
Comments are advisory only and are based on the assumption that the sample and data submitted are valid. Results relate only to the items tested. Missing fluid or component information limits the
evaluation. No warranty is expressed or implied. Measurement uncertainty available upon request.
4/10/24, 4:38 PM State of Utah Mail - St. George Semi-Annual Diesel Reporting
https://mail.google.com/mail/u/0/?ik=36f4379b4d&view=pt&search=all&permthid=thread-f:1787111598196266988&simpl=msg-f:1787111598196266988 1/1
Chad Gilgen <cgilgen@utah.gov>
St. George Semi-Annual Diesel Reporting
1 message
Jim Blankenau <James.Blankenau@imail.org>Wed, Jan 3, 2024 at 3:53 PM
To: Chad Gilgen <cgilgen@utah.gov>
Cc: George McGee <George.McGee@imail.org>, Alan Roberts <Alan.Roberts@imail.org>
Chad,
Please see the attached report for St. George Hospital to meet 40 CFR 60 Dc requirements.
Thanks, Jim
Jim Blankenau, P.G.
Environmental Engineer
Intermountain Health, Canyons
383 W. Vine Street (4th floor), Murray, UT 84124
Mobile: 801.484.6114
NOTICE: This e-mail is for the sole use of the intended recipient and may contain confidential and privileged information.
If you are not the intended recipient, you are prohibited from reviewing, using, disclosing or distributing this e-mail or its
contents. If you have received this e-mail in error, please contact the sender by reply e-mail and destroy all copies of this
e-mail and its contents.
July to Dec 23Boiler Diesel Fuel Compliance SubmissionSigned.pdf
266K
4/10/24, 4:43 PM State of Utah Mail - IHC Subpart Dc Reports Received
https://mail.google.com/mail/u/0/?ik=36f4379b4d&view=pt&search=all&permthid=thread-a:r-1895129688206047432&simpl=msg-a:r-25975318004372…1/1
Chad Gilgen <cgilgen@utah.gov>
IHC Subpart Dc Reports Received
1 message
Chad Gilgen <cgilgen@utah.gov>Wed, Apr 10, 2024 at 4:42 PM
To: James Blankenau <James.Blankenau@imail.org>
Hello Jim,
I apologize for the delay in responding. I wanted to let you know the DAQ is in receipt of the July 2023 - December 2023
Semi-Annual Subpart Dc reports for the following:
IMC
LDS
Logan
McKay Dee
Primary Childrens
Riverton
St. George
TOSH
Utah Valley
Thanks,
Chad
Chad Gilgen | Manager | Minor Source Compliance
385-306-6500 (cell)