HomeMy WebLinkAboutDDW-2024-007703Sanitary Survey - Deficiency Report
PWS Number:UTAH18182 Deficiency Points:75 Survey Date:04/10/2024
Survey Name:USCF - SLC Surveyor:Brian Pattee
Sanitary Survey Category: FW
SDWIS Severity Code: Significant Deficiency
Storage Tanks | ST001 | NORTH 1.5 MG STORAGE TANK
56C. Access opening lid properly gasketed
Rule: R309-545-14(2)Rule requires the access opening to a tank to be furnished with a gasket between the lid
and frame. This significant deficiency must be corrected within 120 days of notification
or have a corrective action plan approved by DDW.
Notes:Small cuts and abrasions in gasket .
Deficiency Points: 25
Days until points become effective on IPS: 120
SDWIS Deficiency Description: V009 STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID AND
FRAME
Sanitary Survey Category: PU
SDWIS Severity Code: Significant Deficiency
Pump Stations | PF001 | DRINKING WATER PUMP STATION
83. There are no unprotected cross-connections in the pump station.
Rule: R309-105-12(1)Cross connections are not allowed unless controlled by an approved and properly
operating backflow prevention assembly or device. This significant deficiency must be
corrected within 120 days of notification or have a corrective action plan approved by
DDW.
Notes:Connection in Pump Station between Culinary System and Fire Water System ( All Fire
Hydrants and all entire complex of Buildings fire suppression systems ) does not have the
approved Backflow Prevention assembly Installed and tested as per the approved plans,
adopted plumbing code and Operating permit from the divison of drinking water.
Deficiency Points: 50
Days until points become effective on IPS: 120
SDWIS Deficiency Description: PS15 PUMP STATION HAS CROSS CONNECTION OR IS SUBJECT TO CONTAMINATION