HomeMy WebLinkAboutDDW-2024-007655
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144830 • Salt Lake City, UT 84114-4830
Telephone (801) 536-4200 • Fax (801) 536-4211 • T.D.D. (801) 903-3978
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Tim Davis
Director
May 9, 2024
Lloyd Marchant
Peoa Pipepline Company
3195 W 5340 N
Peoa, Utah 84061
Subject: Increased Monitoring Requirements – Monthly Source Bacteriological Sampling of
Peoa Spring (WS001); Peoa Pipeline Company, UTAH22013
Dear Lloyd Marchant:
Peoa Pipeline Company is required to conduct source assessment sampling at Peoa Spring (WS001)
to investigate the quality of that source.
This requirement stems from the recent Level 1 Assessment that was submitted on February 23,
2024. Within this Level 1 Assessment, it was stated that there was a chlorinator failure that occurred
in the month of January 2024. In the month of January 2024, there was a total of 10 samples taken
within the distribution system (DS001) 9 of which were total coliform present, E. coli absent. There
were two source samples taken at Peoa Spring (WS001) and both were total coliform present, E.
coli absent. We do not have any recent continuous data for Peoa Spring (WS001) within the last ten
years. It is necessary for the system to collect samples at Peoa Spring (WS001) as described below.
1. Take one bacteriological sample per month at Peoa Spring (WS001) prior to treatment.
The purpose of this source sampling requirement is to gather data to evaluate the quality of
this source.
2. This source sampling requirement shall begin May 2024 and extend at least 18 months for
each month the spring is in operation and accessible, sufficient to cover two peak (or
summer) operating seasons. The Division may evaluate the source sampling requirements
after 18 months based on the data available at that time.
3. This source water quality evaluation has added the following monitoring requirement for
your system:
Facility with
new
requirements
Analyte(s)
Required
# of
samples
Sampling
Frequency
Next Due
Date
Rule
Reference
Peoa Spring
WS001
Total
Coliform; E.
coli
1 Each Monthly 5/31/2024 R309-215-
16(b)
4. All source samples shall be collected prior to any treatment and/or at a location that
represents the source water quality.
5. Label all source samples with the facility name and code (Peoa Spring WS001) listed
above as the sampling location and facility code.
Please note that this source sampling requirement is in addition to the distribution system
bacteriological sampling requirement already in place. All distribution samples must be labeled with
sample location/sample address and DS001 for the facility code. You can find the current
monitoring schedule for your water system at waterlink.utah.gov by selecting your system and then
selecting Water Monitoring under Water System Reports.
Thank you for your efforts in protecting the drinking water quality in your water system and
protecting public health. If you have any questions regarding these increased monitoring
requirements, please contact Sitara Federico of the Division at (385)-515-1459 or
sfederico@utah.gov.
Sincerely,
Mark Berger
Monitoring and Standards Section Manager
cc: Weber-Morgan County Health Department
Sitara Federico, Division of Drinking Water, sfederico@utah.gov
VSA Team, Division of Drinking Water, eqdwvsa@utah.gov