HomeMy WebLinkAboutDAQ-2024-0045761
DAQC-PBR046830002-24
Site ID 4683 (B1) MEMORANDUM
TO: FILE – JAVELIN ENERGY, LLC – 8-24-23-C5-2H MWF
THROUGH: Rik Ombach, Minor Source Oil and Gas Compliance Section Manager
FROM: Fred Goodrich, Environmental Scientist
DATE: January 9, 2024
SUBJECT: OIL AND GAS PERMIT-BY-RULE EVALUATION
INSPECTION DATE: December 12, 2023
SOURCE LOCATION: 8-24-23-C5-2H MWF
Lat: 40.2062 Long: -110.3876
Business Office:
5221 North O'Conner Boulevard, Suite 1100
Irving, TX 75039
SOURCE TYPE: Tank Battery
Duchesne County
API: 4301353826, 4301353903, 4301354052, 4301354053,
4301354084
SOURCE CONTACTS: Greg Simms, Local Contact
Phone: 903-754-4835, Email: gsimms@javelinep.com
Matt Curry, Corporate Environmental Contact
Email: mcurry@javelinep.com
Zach Bertelli, Corporate Environmental Contact
Email: zbertelli@javelinep.com
OPERATING STATUS: Temporarily down
PROCESS DESCRIPTION: Oil and gas products are brought to the surface. These products
go through a separator where the oil and any water products are
sent to storage tanks and the gas is used to power equipment on
site (pump jack engine, tank heater, separator, flare, combustor,
etc.) Any remaining gas is sent to a pipeline that feeds a local gas
plant. The oil and process water in the storage tanks is loaded
into tanker trucks and hauled off site for processing and disposal.
APPLICABLE REGULATIONS: Utah Administrative Code (UAC) R307-500 Series for the Oil
and Gas Industry, and UAC R307-201: Emission Standards:
General Emission Standards; and UAC R307-150: Emission
Inventories, and 40 CFR 60 Subpart JJJJ, 40 CFR 60 Subpart
OOOO.
, -
2
SOURCE EVALUATION: Site Type: PBR-Controlled
Controlled by flare
Site powered by engine
The source registered: 504,323 Estimated Oil BBL.
DOGM current 12 month rolling production is: 16,792 BBL's.
Utah Statute R307-506 requires a source with throughput
greater than 8,000 BBLs to have controls.
REGISTERED EQUIPMENT: Engine - Natural Gas 4-Stroke Lean Burn Make - Caterpillar
Model - G3406TA Mfg Year - 2004 Horse Power - 276
Combustion - Natural Gas, Pneumatic, Tank
3 General Provisions
4 VOC emissions are minimized as reasonably practicable by equipment design, maintenance and
operation practices. [R307-501-4(1)]
In Compliance. DAQ observed and appears to meet these requirements.
5 Air pollution control equipment is designed and installed appropriately, maintained and operated to
control emissions. [R307-501-4(2)]
In Compliance. Appeared to DAQ on wellsite inspection as correctly installed to meet
R307-501-4(2)
6 Vessel vent lines are sloped away from the flare inlet or to a separation vessel (scrubber). [R307-501-2]
In Compliance. Appeared to DAQ on wellsite inspection as correctly installed to design to meet
R307-501-2.
7 Flare inlet lines are equipped with a fire arrestor, pressure gauge, inlet pressure regulating valve and
other components according to the engineering design, the manufacturers specifications or good
practices for safety and emissions control. [R307-501-2]
In Compliance. Appeared to DAQ all components are installed correctly and engineered to
design.
8 Pneumatic Controllers
9 Continuous bleed natural gas-driven pneumatic controllers are in compliance with 40 CFR 60.5390 or
60.5390a as applicable. Exemptions to tagging and record keeping requirements apply to controllers
existing before 12/1/2015. [R307-502-4]
In Compliance. This source does not use continuous bleed controllers as described in 40 CFR
60.5365(d)(1).
10 Flares
11 Any flare has an operational auto-igniter. [R307-503-4]
In Compliance. Auto Igniter in place and operating as designed.
3
12 Tank Truck Loading
13 Truck loading is done by bottom filling or submerged fill pipe [R307-504(1)]
In Compliance. The truck loading area is suitable for submerged loading and it is routine for
truck drivers to load this way.
14 A vapor capture line is used during truck loading if subject to storage vessel emissions controls of
R307-506-4(2). Effective 7/1/2019 for sources existing before 1/1/2018, and upon construction for new
sources.[R307-504-4(2)]
In Compliance. In place and appears operational.
15 Oil and Gas Industry Registration Requirement
16 The source is registered with the DAQ. [R307-505-3(3)]
In Compliance. Observed.
17 Registration has been updated within 30 days of a company name change, removal or addition of
control devices, or termination of operations. [R307-505-3(3)]
In Compliance. Observed.
18 Storage Vessels
19 Thief hatches are kept closed and latched. [R307-506-4(1)]
In Compliance. All hatches were found closed at the start of the evaluation.
20 VOCs from storage vessels are recycled, recovered or controlled by a device that is compliant with
R307-508. Exempt if <8000 bbls crude oil per year, <2000 bbls condensate, or if uncontrolled
emissions are <4 tons VOC per year.[R307-506-4(2)(a)]
In Compliance. Tank emissions are routed to an enclosed combustor.
21 Emissions from emergency storage vessels are controlled according to R307-506-4(2), or are only used
in emergencies, are emptied within 15 days of receiving fluids and are equipped with a liquid level
gauge. [R307-506-4(4)]
In Compliance.
23 Upon modification, the well site was re-evaluated against the thresholds of R307-506-4(2).
[R307-506-4(6)]
In Compliance.
24 Records for each of the following are kept for three years:
Storage vessel vent system inspections (openings, thief hatches, pressure relief devices,
bypasses, etc.), if required
Monthly crude oil throughput
Emission calculations, actuals and sampling data when used to justify an exemption to storage
vessel rules
Emergency storage vessel usage (dates used, emptied, and volumes), if not controlled
per R307-506-4(2)[R307-506-5]
In Compliance. Reviewed at local field office.
4
25 VOC Control Devices
26 The VOC control device(s) required by R307-506 or R307-507 has a control efficiency of 95% or
greater, operates with no visible emissions and has an operational auto-igniter according to R307-503.
[R307-508-3(1)]
In Compliance. Combustor control device met these requirements with no visible opacity.
27 Monthly AVO inspections are conducted on VOC control devices and associated equipment, and
corrective actions are taken within 15 days. [R307-508-3(3)]
In Compliance. The records supplied by the operator met the standards required here.
28 The following records are kept:
VOC control device efficiency, for life of the equipment
Manufacturer operating and maintenance instructions for VOC control devices, for life
of the equipment
AVO inspections of the VOC control device(s), associated equipment and any repairs, for 3 years.
[R307-508-4]
In Compliance. Reviewed at local field office.
29 Leak Detection and Repair
30 The source has an emissions monitoring plan. [R307-509-4(1)(a)]
In Compliance. Observed.
31 The monitoring plan addresses difficult-to-monitor and unsafe-to-monitor components. [R307-509-
4(1)(b)]
In Compliance.
32 If emissions control is required, monitoring surveys are conducted to observe each fugitive emissions
component for fugitive emissions. [R307-509-4(1)(c)]
In Compliance. The operator supplied LDAR inspection forms for review. These inspections
were conducted twice a year, no sooner than 4 months apart and no later than 7 months apart as
required by 40 CFR (60) OOOO and this requirement.
33 Initial monitoring surveys were within 60 days after startup for new sources. Subsequent surveys are
semi-annual for regular components, annual for difficult-to-monitor components, and as required by
the monitoring plan for unsafe-to-monitor components. [R307-509-4(1)(d)]
In Compliance. The records supplied by the operator met the standards required here.
34 Monitoring surveys are done with OGI equipment or by Method 21. [R307-509-4(1)(e)]
In Compliance. The operator uses a Flir GF 320 OGI camera.
35 Fugitive leaks are repaired within 15 days unless infeasible, unsafe, etc., as stated in the rule, which
require repair within 24 months per the rule. [R307-509-4(1)(f)]
In Compliance. The records supplied by the operator met the standards required here.
36 Resurvey of the repaired components is completed within 30 days. [R307-509-4(1)(g)]
In Compliance. The records supplied by the operator met the standards required here.
5
37 The following records are kept:
The emissions monitoring plan, for life of the site
LDAR inspections, repairs and resurveys, for 3 years [R307-509-5]
In Compliance. Observed.
38 Natural Gas Engines
39 Engines subject to R307-510 (does not have an AO, began operations, installed or modified after
January 1, 2016) meet the following limits:
Maximum Engine hp Emission Standards in (g/hp-hr)
NOx CO VOC HC+NOx
>25 hp and < 100 hp - 4.85 - 2.83
>100 hp 1.0 2.0 0.7 -
In Compliance. Operators records are compliant.
40 Affected engines are certified or have an initial performance test per 40 CFR 60.4244. [R307-510-4(2)]
In Compliance. Operators initial performance tests meet the criteria.
41 Affected engine exhaust vents are vertical and unrestricted.
Stacks are 8' or greater if the site horsepower rating is 151 to 305
Stacks are 10' or greater if the site horse power rating is 306 or greater. [R307-510-4(3)]
In Compliance. Installed correctly.
42 Engine certifications or initial performance tests required are kept for the life of the engine at the
source. [R307-510-5]
In Compliance. Observed.
43 Associated Gas Flaring
44 Associated gas is routed to a process unit for combustion, a sales pipeline or an operating VOC control
device, except in an emergency.
An emergency release is unanticipated, temporary, infrequent, unavoidable, =24 hrs. and is not
due to operator negligence.
Low pressure gas from working loss, breathing loss and oil flashing is not
"associated gas". [R307-511-4(1)]
In Compliance. No reported venting events or breakdowns
45 The following records are kept:
The time and date of event
Volume of emissions
Any corrective action taken for 3 years.[R307-511-5(1)(a)(b)]
In Compliance. Observed.
6
46 Visible Emissions
47 Visible emissions, except for unavoidable irregularities that do not exceed three minutes, are within the
following opacity limits:
Installations constructed on or before 4/25/1971 40%
Installations constructed after 4/25/1971 20%
Gasoline engines 0%
Diesel engines manufactured after 1/1/1973 20%
Diesel engines manufactured before 1/1/1973 40%
Note: Required VOC control devices shall have no visible emissions per R307-508-3.[R307-201-3]
In Compliance. No visible emissions were detected.
55 Emission Inventory:
56 An emissions inventory has been submitted within the past three years. [R307-150-9(1)]
In Compliance. The operator submitted for the 2020 emissions inventory.
59 NSPS (Part 60) JJJJ: Standards of Performance for Stationary Spark Ignition Internal Combustion
Engines [40 CFR 60 Subpart JJJJ]
In Compliance. Operator meets the standards set forth.
60 NSPS (Part 60) OOOO: Standards of Performance for Crude Oil and Natural Gas Production,
Transmission and Distribution [40 CFR 60 Subpart OOOO]
In Compliance. Operator meets the standards set forth.
PREVIOUS ENFORCEMENT
ACTIONS: No enforcement actions within the past five years.
COMPLIANCE STATUS &
RECOMMENDATIONS: In regards to: 8-24-23-C5-2H MWF: In Compliance - Wellsite
down on compressor upgrade. This source was found to be clean
and well-kept with no visible or fugitive emissions. The source
was inspected by AVO and with an OGI camera and found to be
free of leaks. The operator's representatives were pleasant and
cooperative. Requested records were provided in a timely
manner and reviewed at the local field office.
RECOMMENDATION FOR
NEXT INSPECTION:
The DAQ recommends frequency of inspections remain current
as scheduled. In Compliance.
ATTACHMENTS: None.