HomeMy WebLinkAboutDERR-2024-004580Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name INTERMOUNTAIN ST. GEORGE REGIONAL
MEDICAL CENTER
Address 544 S 400 E
SAINT GEORGE, UT 84770
Contact INTERMOUNTAIN ST. GEORGE REGIONAL
MEDICAL CENTER
Phone
Email George.McGee@imail.org
TANK LOCATION
Name DIXIE MEDICAL CENTER
Address 544 S 400 E
SAINT GEORGE, UT 84770
A Operator MICHAEL WEBB
Phone (435) 680-2477
B Operator SAME
Phone SAME
Facility ID: 6000087 Inspection Date: 02/28/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
TANK DETAILS
Tank ID/Alt ID 4 / 4
E-Gen/AST Yes / No
Siphon/Compart No / No
Tank Status Temporarily Out of Use
Installed/Cap/Loc June 10, 1997 / 600 / North
Substance
Stored Diesel /
Tank Material-
Mod
Fiberglass Reinforced Plastic-
Double-Walled
ATG Veeder Root / TLS-300 CSLD No
Manifold
LTT Test None
LLD Test None
Pipe Material-Mod Flexible Plastic / Double-
Walled
Pipe type/STP Cont U.S. Suction / No
STP Flex
Connectors Steel Flex in Sump
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Overfill
alarm / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel Det
CP Tank Test None
CP Pipe Test None
Tank ID/Alt ID 5 / 5
E-Gen/AST Yes / No
Siphon/Compart No / No
Tank Status Temporarily Out of Use
Installed/Cap/Loc June 10, 1997 / 1000 / South
Substance
Stored Diesel /
Tank Material-
Mod
Fiberglass Reinforced Plastic-
Double-Walled
ATG Veeder Root / TLS-300 CSLD No
Manifold
LTT Test None
LLD Test None
Pipe Material-Mod Flexible Plastic / Double-
Walled
Pipe type/STP Cont U.S. Suction / No
STP Flex
Connectors Steel Flex in Sump
LLD Model
Spill/Overfill/Sm
Delivery
5 gal. Spill Bucket / Overfill
alarm / No
PST Fund/Other
Type Yes / None
Tank/Pipe Rel Det
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
None
2024-02-28 Page 1 of 4
FACILITY RESPONSES
The above accurately represents the
facility's release detection records Yes
Financial Responsibility
Financial responsibility method is ok?Yes
Operator Training
A Operator current?Yes
B Operator current?Yes
Monthly checklist available and
complete?Yes
TANK RESPONSES
Tank 4 Temporary Closure
Is release detection being maintained
or is the depth of product less than 1
inch?
No
What is the depth of product? (Inches)2
The cathodic protection system being
maintained?Yes
The tanks are locked and secured?Yes
Tank 4 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
Tank 5 Temporary Closure
Is release detection being maintained
or is the depth of product less than 1
inch?
Yes
What is the depth of product? (Inches)<1
The cathodic protection system being
maintained?Yes
The tanks are locked and secured?Yes
Tank 5 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
Yes
Does the overfill device have a valid 3-
year test or the tank is exempt?Yes
Tank 4 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Tank 4 Suction Piping Leak Detection
U.S. suction piping has a valid LTT
every 3 years or monthly monitoring?Yes
Tank 5 Cathodic Protection
Tanks are protected from corrosion?Yes
Piping is protected from corrosion?Yes
Flex connectors at the tank sub-pumps
are protected from corrosion?Yes
Tank 5 Suction Piping Leak Detection
U.S. suction piping has a valid LTT
every 3 years or monthly monitoring?Yes
DISPENSER RESPONSES
2024-02-28 Page 2 of 4
Prepared by fueloperator.com
MONTHLY LEAK DETECTION MONITORING
Feb '23 Mar '23 Apr '23 May '23 Jun '23 Jul '23 Aug '23 Sep '23 Oct '23 Nov '23 Dec '23 Jan '24
Tank 4 Not Avail Not Avail Not Avail Not Avail Not Avail Not Avail Not Avail Not Avail Not Avail Not Avail Not Avail Not Avail
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Tank 5 Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
TANK 4
No Photos
Question:Is release detection being maintained or is the depth of product less than 1 inch?
Comments:None
Inspection Information
Inspector:Saathoff, Rick
Record Created:Feb. 28, 2024, 1:15 p.m.
Inspection Date:Feb. 28, 2024
2024-02-28 Page 3 of 4
2024-02-28 Page 4 of 4