HomeMy WebLinkAboutDERR-2024-006449Utah Department of Environmental Quality - UST Release Detection
TANK OWNERSHIP
Name RAMSAY OIL CO
Address PO BOX 99
ORDERVILLE, UT 84758
Contact RAMSAY OIL CO
Phone
Email genoramsay@yahoo.com
TANK LOCATION
Name RAMSAY OIL
Address 4490 S. STATE ST.
ORDERVILLE, UT 84758
A Operator None
Phone None
B Operator SAME
Phone SAME
Facility ID: 6001048 Inspection Date: 04/17/2024
DISPENSER DETAILS
DISP
ID/ALT
ID
SUBSTANCE UDC PIPE FLEX LOC
INSTALL
DATE
UDC
INSTALL
DATE
FIRE
VALVE
SAT
PRESENT
UDC
TEST
DISP
FLEX
CP
TEST
TANK DETAILS
Tank ID/Alt ID 1 / 1
E-Gen/AST No / Yes
Siphon/Compart No / No
Tank Status Currently In Use
Installed/Cap/Loc Jan. 1, 1910 / 10000 /
Substance
Stored Diesel /
Tank Material-
Mod
Asphalt Coated or Bare Steel-
Secondary Containment
ATG /
LTT Test None
LLD Test None
Pipe Material-Mod Bare Steel / Secondary
Containment
Pipe type/STP Cont Pressurized / No
STP Flex
Connectors Not in contact with soil
LLD Model
Spill/Overfill/Sm
Delivery / / No
PST Fund/Other
Type No / None
Tank/Pipe Rel Det TankLDNotListed
PipeLDNotListed
CP Tank Test None
CP Pipe Test None
INSPECTION COMMENTS
None
2024-04-18 Page 1 of 3
FACILITY RESPONSES
The above accurately represents the
facility's release detection records Yes
Financial Responsibility
Financial responsibility method is ok?Yes
TANK RESPONSES
Tank 1 Pressure Piping Leak Detection
Does the pressurized piping system
have a valid annual line tightness test
or valid monthly monitoring?
No
Tank 1 Spill/Overfill
Tank has a spill prevention device?Yes
Are you able to visually inspect the spill
containment bucket(s) for functionality?
(i.e. are the buckets clean enough to
see cracks, etc?)
Yes
Is the spill containment bucket intact?Yes
Tank 1 Spill/Overfill
Does the spill bucket have a valid 3-
year test, valid monthly monitoring for
DW buckets, or the tank is exempt?
No
DISPENSER RESPONSES
MONTHLY LEAK DETECTION MONITORING
Apr '23 May '23 Jun '23 Jul '23 Aug '23 Sep '23 Oct '23 Nov '23 Dec '23 Jan '24 Feb '24 Mar '24
Tank 1 Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
Line Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl Not Appl
NON-COMPLIANCE ITEMS
TANK 1
No Photos
Question:Does the pressurized piping system have a valid annual line tightness test or valid monthly
monitoring?
Comments:None
TANK 1
No Photos
Question:Does the spill bucket have a valid 3-year test, valid monthly monitoring for DW buckets, or the tank is
exempt?
Comments:None
2024-04-18 Page 2 of 3
Prepared by fueloperator.com
Inspection Information
Inspector:Viehweg, Kim
Record Created:April 18, 2024, 8:50 a.m.
Inspection Date:April 17, 2024
2024-04-18 Page 3 of 3
Underground Storage Tank Inspection Verification Form
Facility ID:6001048
Owner Name:RAMSAY OIL CO Facility Name:RAMSAY OIL
Owner Address:PO BOX 99 Street Address:4490 S. STATE ST.
ORDERVILLE, UT 84758 ORDERVILLE, UT 84758
Operator A:No Data / No Data / Operator B:No Data / No Data /
Owner Email:genoramsay@yahoo.com UTM Coordinates X/Y:350880 / 4121123
Disp ID/Alt
ID
Substance UDC Pipe Flex Loc Install Date UDC Install Date Fire
Valve
Sat
Present
UDC Test Disp Flex CP
Test
1 - 1/2 Diesel No Booted Steel Flex Yes No
2 - 3/4 Diesel No Booted Steel Flex Yes No
3 - 5/6 Diesel No Booted Steel Flex Yes No
Tank ID/Alt ID:1 / 1 EGen/AST/Stat
e:
No / Yes /
Yes
Pipe Material-Mod:Bare Steel - Secondary Containment
Siphon/Compart:No / No PVV/StageI:Pipe Type/STP Cont:Pressurized / No
Tank Status:Currently In Use STP Flex Connectors:Not in contact with soil
Installed/Cap/Loc:1/1/1910 / 10000 / LLD Model:
Substance Stored:Diesel / Spill/Overfill/Sm deliv: / / No
Tank Material-Mod:Asphalt Coated or Bare Steel - Secondary
Containment
PST Fund/Other Type:No /
ATG: / Tank/Pipe Rel Det:OTHER / OTHER / NONE
ATG Specs: / / STP Sump Test:Spill Bk Test:
ATG Test:Overfill Test:
LTT Test:LLD Test:CP Tank Test:CP Pipe Test:
4/24/2024 Page 1 of 1