February 13, 2024
Matthew Robinson
Smithfield Hog Rocky Mtn-Blue Mtn South
PO BOX 100
Milford, UT 84751
Subject: Notice of Source Reactivation, Increased Monitoring Requirements for
Smithfield Hog Rocky Mtn-Blue Mtn South; UTAH11066
Matthew Robinson:
On January 24, 2024, after submitting the samples required under R309-205, you notified the
Division of Drinking Water (the Division) that the Blue Mtn South Well 3 (identified as WS003)
had been reactivated. This changes the monitoring requirements for this water system.
To account for the increased loads of Arsenic filtered through the systems thirteen point of use
(POU) devices, one Arsenic sample, analyzed by a certified laboratory, will be expected from
one POU device per month. Please rotate these monthly samples through six different POU
devices. After six months, this requirement can be reduced back to 2 Arsenic samples analyzed
by a certified laboratory per year. Once this requirement has been fulfilled, please notify David
Kruse at 385-566-7789 or dbkruse@utah.gov.
Additionally, please continue to take surrogate Arsenic samples as specified in the operating
permit for the POU devices.
The updated monitoring requirements are reflected in the table below, and are available to view
anytime at your systems monitoring page on waterlink.utah.gov.
Facility with new
requirements
Analyte(s)
Required
# Of
sampl
es
Sampling
Frequency Next Due Date Rule Reference
TPPOU
Arsenic Removal Arsenic 1 Monthly 02/01/2024-
02/29/2024 R309-205-5
Matthew Robinson
Page 2 of 2
February 13, 2024
WS003
Blue Mtn South Well 3
Inorganics and
Metals 1 Every Three
Years
01/01/2026-
12/31/2028
R309-205-
5(3)(a)
Nitrate 1 Yearly 01/01/2024-
12/31/2024
R309-205-
5(4)(a)
Sulfate, Sodium,
TDS 1 Every Three
Years
01/01/2026-
12/31/2028
R309-205-
5(3)(a)
Volatile Organics 1 Every Three
Years
01/01/2026-
12/31/2028 R309-205-6(2)
Pesticides 1 Every Three
Years
01/01/2026-
12/31/2028 R309-205-6(1)
Thank you for your efforts in maintaining a safe drinking water system. If you have questions
concerning your sampling requirements, please contact David Kruse at 385-566-7789
(dbkruse@utah.gov).
Sincerely,
Mark Berger
Monitoring and Standards Implementation Manager
cc: Matthew Robinson, Smithfield Hog Rocky Mtn-Blue Mtn South, mrobinson@smithfield.com
Jeremy Roberts, Southwest Utah Health Department, jroberts@swuhealth.org
Paul Wright P.E., Department of Environmental Quality, pwright@utah.gov
Mark Berger, Division of Drinking Water, mberger@utah.gov
David Kruse, Division of Drinking Water, dbkruse@utah.gov