HomeMy WebLinkAboutDDW-2024-006078
195 North 1950 West • Salt Lake City, UT
Mailing Address: P.O. Box 144830 • Salt Lake City, UT 84114-4830
Telephone (801) 536-4200 • Fax (801) 536-4211 • T.D.D. (801) 903-3978
www.deq.utah.gov
Printed on 100% recycled paper
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
Lieutenant Governor
Department of
Environmental Quality
Kimberly D. Shelley
Executive Director
DIVISION OF DRINKING WATER
Nathan Lunstad P.E.
Director
February 13, 2024
Katherine Munns
Portage Town Water System
PO Box 4
Portage, UT 84331
Subject: Emergency Source Designation for Portage Town Water System; UTAH02012
Katherine Munns:
It was recently discovered that the 1978 Well (identified as WS003) does not combine with the
South Canyon Spring (WS001) and the Upper Spring (WS004) prior to entering the Portage Town
Water System’s distribution system. In accordance with R309-205, this source is now required to
be sampled independently as a separate point of entry.
In January 2024 you informed the Division of Drinking Water (the Division) that the 1978 Well
(WS003) acts solely as an emergency source, and that it had only been used twice within the past
ten years. Given this, you requested that the Division designate the 1978 Well (WS003) as an
emergency source. Emergency sources are only required to complete a full suite of source analysis
once every nine years, and shall only be used in the event of an actual emergency.
This source has not been tested independently since 2013. For this reason, before the 1978 Well
(WS003) can be designated and utilized as an emergency source, the system must collect the
following samples by July 31, 2024:
Facility with new
requirements Analyte(s) Required # of
samples
Sampling
Frequency
Next Due
Date
Rule
Reference
WS003 1978 Well Inorganics & Metals 1 Every Nine
Years 07/31/2024 R309-205-
5(3)(a)
Nitrate 1 Every Nine
Years 07/31/2024 R309-205-
5(4)(a)
Sulfate, Sodium, TDS 1 Every Nine
Years 07/31/2024 R309-205-
5(3)(a)
Katherine Munns
Page 2 of 2
February 13, 2024
Pesticides 1 Every Nine
Years 07/31/2024 R309-205-
6(1)(d)
Radionuclides 1 Every Nine
Years 07/31/2024 R309-205-
7(1)(b)
Volatile Organic
Contaminants 1 Every Nine
Years 07/31/2024 R309-205-
6(2)
BacT 1 One Time 07/31/2024
Please label samples collected from the 1978 Well as WS003 on all laboratory paperwork. Once
the sample results have been received, the routine monitoring frequency for this source will be one
sample, for each of the analytes listed above, every nine years. Please contact David Kruse at 385-
566-7789 or dbkruse@utah.gov with any questions or concerns about the sampling requirements
given above.
Sincerely,
Mark Berger
Monitoring and Standards - Implementation Manager
cc: Katherine Munns, Portage Town Water System, prtgwatermaster@gmail.com
Grant Koford, Bear River Health Department, gkoford@brhd.org
Mark Berger, Division of Drinking Water, mberger@utah.gov