HomeMy WebLinkAboutDDW-2024-006007Contacts
Type: Administrative Contact
Name: MICHAEL ZETLINGER
Office: 701-425-2387
Emergency:
Email:
aspenacresassociation@gmail.com
Site Information
Legal Contact: ASPEN ACRES
ASSOCIATION
Address: P.O. BOX 429 , OAKLEY,
UT 84055
Phone: 435-783-7392
County: SUMMIT COUNTY
System Type: Transient Non-
Community
Certification Required:
Total Population: 192
Site Updates
Last Inventory Update: 06/09/2022
Last Surveyor Update: 05/19/2022
Surveyor: SARAH ROMERO
Operating Period: 1/1 - 12/31
Last IPS Update: 10/26/2023 20:49:51
Political Districts
Representative: 53
Senate: 26
Water Usage Information per ERC
Total Ips Points: 425
Public Water System IPS ReportDEQ | Drinking Water
Aspen Acres Association PWS ID: UTAH22061 Rating: Approved 11/22/2010 Status: Active
IPS SUMMARY Total IPS Points: 425
Admin & Physical Facilities Quality & Monitoring Significant Deficiency Violations
175 0 250
PHYSICAL FACILITY POINTS Total Pts: 175
Facility Facility Name Status Points Effective Details
DS001 UTAH22061 DISTRIBUTION SYSTEM A 30 Hide Details ( 3 )
Code Description Severity Comments Determined
Date Pending Assessed
M006
CCC-LACKS WRITTEN
RECORDS OF CCC
ACTIVITIES
MIN The operator will be starting compiling records and will
be sending these records as soon as they are compiled.05/19/2022 0 15
M007
CCC-LACKS ON-
GOING
ENFORCEMENT
IMPLEMENTATION
MIN The operator will be starting compiling records and will
be sending these records as soon as they are compiled.05/19/2022 0 15
S094
SYSTEM LACKS MORE
THAN 20% OF
REQUIRED SOURCE
CAPACITY
SIG
TEMPORARY EXCEPTION GRANTED 2/25/2021.
SYSTEM MUST CORRECT DEFICIENCY OR
RENEW EXCEPTION BY 12/31/2026. FILE #12002
08/21/2019 50 0
ST001 STORAGE FACILITY ST001 A 25 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
V010
STORAGE TANK LID
NOT SHOEBOX
STYLE
SIG Bolted lid- not a shoe box type with at least 2 inches.
Recommend to apply for an exception.05/19/2022 0 25
ST002 STORAGE FACILITY ST002 A 25 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
V010
STORAGE TANK LID
NOT SHOEBOX
STYLE
SIG Bolted lid- not a shoe box type with at least 2 inches.
Recommend to apply for an exception.05/19/2022 0 25
ST003 50,000 GALLON CONCRETE TANK A 25 Hide Details ( 1 )
Code Description Severity Comments Determined
Date Pending Assessed
V009
STORAGE TANK LID
LACKS A
FUNCTIONING
GASKET BETWEEN
THE LID AND FRAME
SIG It has a gasket but needs a replacement.05/19/2022 0 25
WS001 ASPEN ACRES SPRING A 70 Hide Details ( 6 )
Code Description Severity Comments Determined
Date Pending Assessed
SS12
SPRING BOX ENTRY
NOT ELEVATED AT
LEAST 18 INCHES
ABOVE EARTHEN
COVER
MIN The upper spring box is buried. The system may want to
apply for an exception to the rule.05/22/2013 0 15
SS02 SPRING COLLECTION
AREA NOT FENCED MIN
TEMPORARY EXCEPTION GRANTED. SYSTEM
MUST CORRECT DEFICIENCY OR RENEW
EXCEPTION BY 6/30/2025. FILE #13046
05/19/2022 15 0
SS09
SPRING BOX LID
NOT SHOEBOX
STYLE
SIG Spring box (diffuser box) does not have shoebox-type lid.05/19/2022 0 25
SS08 ROOTS IN SPRING
COLLECTION PIPES SIG The junction box is underground- cannot see if roots are
present.05/19/2022 0 25
SSL2 VENT NOT PRESENT REC 07/02/2007 0 0
L014 SPRING COLLECTION
BOX NOT PRESENT MIN 08/21/2019 0 5
SIGNIFICANT DEFICIENCY VIOLATIONS Total Pts: 250
ID Violation Code Deficiency Determined
Points
Effective
ST003
45 FAILURE ADDRESS
DEFICIENCY (GWR)
V009
STORAGE TANK LID LACKS A FUNCTIONING GASKET
BETWEEN THE LID AND FRAME
10/26/2023 50
WS001
45 FAILURE ADDRESS
DEFICIENCY (GWR)
SS08 ROOTS IN SPRING COLLECTION PIPES 10/26/2023 50
WS001
45 FAILURE ADDRESS
DEFICIENCY (GWR)
SS09 SPRING BOX LID NOT SHOEBOX STYLE 10/26/2023 50
ST001
45 FAILURE ADDRESS
DEFICIENCY (GWR)
V010 STORAGE TANK LID NOT SHOEBOX STYLE 10/26/2023 50
ST002
45 FAILURE ADDRESS
DEFICIENCY (GWR)
V010 STORAGE TANK LID NOT SHOEBOX STYLE 10/26/2023 50
LEAD COPPER MONITORING AND QUALITY VIOLATIONS Total Pts: 0
Violation No.Period Code Description/Name Points Effective
CHEMICAL MONITORING RULE VIOLATIONS Total Pts: 0
Facility Violation No Period Code Violation Type Analyte Group Determined Seasonality Points Effective
TREATMENT VIOLATIONS Total Pts: 0
Facility Violation No Period Code Violation Type Analyte Group Determined Points Effective
MICROBIAL RULE VIOLATIONS
Date Range Start: 10/01/2022
Total Pts: 0
Determine Date Compliance Period Code Violation Type Return To Compliance Points Effective
OPERATOR CERTIFICATION
Type Level Required Highest Certificate
Distribution
Treatment
CONSUMER CONFIDENCE REPORT Total Effective Points: 0
Violation No.Period Code Description/Name Points Effective
PUBLIC NOTIFICATION VIOLATIONS Total Pts: 0
Violation No.Date Code Description/Name Points Effective
IPS COMPLIANCE SCHEDULES
Type Required Activities Severity Created Due
CORRECTIVE ACTION
PLAN
STORAGE TANK LID NOT SHOEBOX STYLE SIG 06/08/2022 09/01/2023
CORRECTIVE ACTION
PLAN
ROOTS IN SPRING COLLECTION PIPES SIG 06/08/2022 09/01/2023
CORRECTIVE ACTION
PLAN
SPRING BOX LID NOT SHOEBOX STYLE SIG 06/08/2022 09/01/2023
CORRECTIVE ACTION
PLAN
SPRING COLLECTION AREA NOT FENCED MIN 06/08/2022 06/30/2025
CORRECTIVE ACTION
PLAN
STORAGE TANK LID NOT SHOEBOX STYLE SIG 06/08/2022 09/01/2023
CORRECTIVE ACTION
PLAN
STORAGE TANK LID LACKS A FUNCTIONING GASKET BETWEEN THE LID
AND FRAME
SIG 06/08/2022 09/01/2023
TEMPORARY EXCEPTION SYSTEM LACKS MORE THAN 20% OF REQUIRED SOURCE CAPACITY SIG 08/21/2019 12/31/2026